Actions

Difference between revisions of "AlphaCom XE1"

From Zenitel Wiki

(Factory Reset (coldstart))
(Remote Control Inputs and outputs)
 
(130 intermediate revisions by 3 users not shown)
Line 1: Line 1:
[[Image:XE1.PNG|thumb|350px|AlphaCom XE1 Audio Server with HD Voice]]
+
<table style="float:right; max-width:80%; border-style: double; border-color: #c7c7c7;">
 +
<tr style="rowspan:2;">
 +
<td style="display: block; vertical-align: bottom;">[[Image:XE1.PNG|350px]]</td>
 +
</tr>
 +
<tr>
 +
<td style='background-color:#efefef;'>AlphaCom XE1 Audio Server with HD Voice</td>
 +
</tr>
 +
</table>
  
=Highlights=
+
==Highlights==
 
* Made to provide critical communication in any environment
 
* Made to provide critical communication in any environment
 
* Supports 552 IP stations
 
* Supports 552 IP stations
Line 8: Line 15:
 
* Fully compatible with any AlphaCom system
 
* Fully compatible with any AlphaCom system
  
=Mounting & Dimensions=
+
==Connectors==
The cabinet should be mounted on a shelf or in a 19” rack. It contains one AMC-IP processor board only. The server includes a power board.
+
[[Image:XE1 eth serial.png|thumb|left|700px]]
 
+
<br style="clear:both;"/>
[[File:XE1FrontView.PNG|500px|left|thumb|Front View]]
 
<br style="clear:both;" />
 
[[File:XE1RearView.PNG|500px|left|thumb|Rear View]]
 
<br style="clear:both;" />
 
[[File:XE1TopView.PNG|500px|left|thumb|Top View]]
 
<br style="clear:both;" />
 
  
=Connections=
 
[[File:XE1 Connections.png|thumb|left|500px]]
 
<br style="clear:both;"/>
 
 
===Power===
 
===Power===
The exchange is normally powered from 90-240VAC via a 5VDC power supply adapter.
+
The AlphaCom XE1 is powered by 5VDC from 90-240VAC power adapter. The power adapter comes with the XE1 server.
  
 
===Network===
 
===Network===
Two RJ-45 Ethernet terminals are used for IP LAN, WAN, Internet and AlphaNet IP communication. Eth0 is also used for programming.
+
The XE1 server has two RJ-45 ethernet ports for IP communication. Ethernet port 0 (Eth 0) is by default configured as a Management port, allowing connection to the embedded web server ([[AlphaWeb]]) and connection of the PC configuration tool [[AlphaPro]].
 +
Default IP addresses:
 +
* Eth0 has IP address 169.254.1.5
 +
* Eth1 gets IP address from DHCP by default
  
 
===Serial Ports===
 
===Serial Ports===
The serial ports with RS232 and RS422/RS485 interfaces are used for connecting to equipment using these protocols
+
<table style="float:right; max-width:80%; border-style: double; border-color: #c7c7c7;">
 +
<tr style="rowspan:2;">
 +
<td style="display: block; vertical-align: bottom;">[[Image:Serial ports XE1.PNG|350px]]</td>
 +
</tr>
 +
<tr>
 +
<td style='background-color:#efefef;'>XE1 Serial ports pinout</td>
 +
</tr>
 +
</table>
 +
Serial ports can be used for communication with external equipment. There are two serial ports:
 +
* '''Serial Port 0''': R232 on an 9-Pin D-sub connector
 +
* '''Serial Port 1''': RS232, RS422 or RS485 on an RJ45 connector
 +
** '''RS232:''':  [[AMC-IP_-_AlphaCom_Processor_Board_(Black)#Switches_and_Jumpers|Switch 8 on S601]] on the AMC-IP board must be set to OFF (default).
 +
** '''RS422''': [[AMC-IP_-_AlphaCom_Processor_Board_(Black)#Switches_and_Jumpers|Switch 8 on S601]] on the AMC-IP board must be set to ON. Jumpers J1 and J2 in position 1-2
 +
** '''RS485''': [[AMC-IP_-_AlphaCom_Processor_Board_(Black)#Switches_and_Jumpers|Switch 8 on S601]] on the AMC-IP board must be set to ON. Jumpers J1 and J2 in position 2-3 (default)
  
[[File:XEsmallConnections.png|thumb|left|500px|XE1 IP and serial connections]]
+
To access the jumpers J1 and J2, remove the top lid of the XE1 server:
<br style="clear:both;" />
+
<table style="max-width:80%; border-style: double; border-color: #c7c7c7;">
 +
<tr style="rowspan:2;">
 +
<td style="display: block; vertical-align: bottom;">[[Image:SerialPortJumpers XE1.png|350px]]</td>
 +
</tr>
 +
<tr>
 +
<td style='background-color:#efefef;'>Jumpers J1 and J2 for selection of <br>RS422 or RS485 for Serial Port 1</td>
 +
</tr>
 +
</table>
  
====Serial Port 0====
+
== Installation ==
9-Pin D-sub (RS232 Only)
+
* Remove the front cover of the XE1 cabinet
:No additional settings necessary
+
* Prepare the AMC-IP board with the STIC according to [[AMC-IP - AlphaCom Processor Board (Black)|this article]], then insert the AMC-IP board into the server. Give the board a firm final push to make sure it goes all the way into position.
  
----
+
{{obs|
 +
* ''Turn '''power off''' before inserting or removing the AMC-IP board'' }}
  
====Serial Port 1====
+
* Insert the plug from the power adapter. Make sure that the cable goes underneath the strain relief.
RJ45 (RS232/422/485)
+
* Insert the power adapter to the mains socket.
 +
* Watch the LEDs of the AMC-IP board. The system uses approx. 70 seconds to start up. When running the green status LED should be flashing.
 +
* Connect a laptop to Eth 0 port, open a web browser (e.g. Firefox or Chrome), and log on to the web server using IP address 169.254.1.5. (Default Username/Password = admin/alphaadmin)
 +
* [[AMC-IP software upgrade (Black AMC-IP board)|Upgrade the software]] of the server to the latest version. Upgrade is done from the web interface of the server. This will ensure that the system has the latest features, bug fixes and security updates.
 +
* Replace the front cover of the XE1 cabinet
  
:Additional settings:
+
== Configuration==
:'''RS232:'''
+
* [[AlphaPro]] is the Windows application used for configuring the AlphaCom XE system. Configuration of user data, such as Directory Numbers, Direct Access Keys, Group Calls etc. is done from AlphaPro.
:* [[AMC-IP_-_AlphaCom_Processor_Board_(Red)#Switches_and_jumpers|Switch 8 on S601]] on the AMC-IP board must be set to OFF.
+
* [[AlphaWeb]] is the embedded web server running on AlphaCom XE. The AlphaWeb server provides functions for system monitoring, system configuration, and system upgrade. Initial connection is done by connecting a laptop to Eth 0 port, open a web browser (e.g. Firefox or Chrome), and log on to the web server using IP address 169.254.1.5. (Default Username/Password = admin/alphaadmin).
  
:'''RS422/485:'''
 
:* [[AMC-IP_-_AlphaCom_Processor_Board_(Red)#Switches_and_jumpers|Switch 8 on S601]] on the AMC-IP board must be set to ON.
 
:* Take off the top lid to reach the jumpers inside, and set them to the correct position.
 
::- RS485: Both jumpers in position 2-3 (default)
 
::- RS422: Both jumpers in position 1-2
 
  
[[File:SerialPortJumpers XE1.png|thumb|left|300px|RS422/485 selector for Serial Port 1 in the XE1]]
+
==Factory Reset (coldstart)==
<br style="clear:both;" />
+
<table style="max-width:80%; border-style: double; border-color: #c7c7c7;">
 +
<tr style="rowspan:2;">
 +
<td style="display: block; vertical-align: bottom;">[[Image:AMC-IP ColdStartButton.png|300px]]</td>
 +
</tr>
 +
<tr>
 +
<td style='background-color:#efefef;'>Cold start button on AMC-IP board</td>
 +
</tr>
 +
</table>
  
==Remote Control Inputs (RCI)==
 
===Connections===
 
There are two inputs for clean contacts on the [[RCI - Remote Contol Input|RCI connectors]] which can execute programmable functions. Note that the cabinet needs to be opened to get access to these connectors
 
[[File:XE1 RCI.jpg|left|thumb|300px|RCI inputs in an AlphaCom XE1 (top lid removed)]]
 
<br style="clear:both;" />
 
  
===Configuration===
+
===Cold start procedure===
In [[AlphaPro]] there is an [[Exchange_%26_System_%28AlphaPro%29#RCI|RCI table]], where the physical address of the input is entered, along with the desired actions. The physical address is given as [[device]] + pin-number.
+
This procedure will delete all previous programming, load factory default settings and set the IP-address to 169.254.1.5 with mask 255.255.0.0 on Eth0.
 +
* Press and hold the cold start button on the AMC-IP board, then power up the XE1 server.
 +
* Keep the cold start button pressed for at least 2 seconds after power on, then release the button.  
 +
* The AMC-IP status LED will flash green when the server is up and running
  
The RCI table supports up to 140 inputs.
+
=== Cold-start of intercom application only, keep the IP settings ===
* For internal RCIs in the AlphaCom XE1, the device address is 65, and the pin number is 1-2.  
+
This procedure will delete all intercom configuration (i.e. delete all AlphaPro configuration), but keep all IP Settings (AlphaWeb configuration).
* Internal pin number 8 is the [[Temperature Alarm|temperature alarm]] (not used in XE1).
+
*Power up the AlphaCom XE1 server
* Mappings for the internal RCI's are [[Autoload|autoloaded]]. Mappings for external RCI's (Slave modules, RIO's or IPARIO) must be manually programmed.
+
*After 10 seconds, press and hold the cold start button on the AMC-IP board.
 +
*Keep the cold start button pressed until the AMC-IP status LED is flashing green.
  
{| border="1"
+
===Other methods of factory default===
! style="background:#ffdead;" width="150" |&nbsp;
+
The server can be set to factory default values also:
! style="background:#ffdead;" width="80" |RCI Type
+
* '''From [[AlphaWeb]]''': System Maintenance -> System Recovery -> Load Factory Defaults
! style="background:#ffdead;" width="150" |Device/Station physical Number
+
* '''From [[AlphaPro]]:''' Upload a default AlphaPro database to the exchange
! style="background:#ffdead;" width="100" |Pin Number
 
|-
 
| AlphaCom XE1 || align=center | Device || align=center | 65 || align=center | 1 - 2
 
|-
 
|}
 
  
===Example===
+
<br><br>
<big>Start fire alarm message and activate rotating lamp:</big>
 
[[File:RCI Conf Example1.PNG|left|800px]]
 
<br style="clear:both;" />
 
  
[[File:RCI Conf Example2.PNG|left|500px]]
+
==Software upgrade==
<br style="clear:both;" />
+
* It is highly recommended to [[AMC-IP software upgrade (Black AMC-IP board)|upgrade the software]] of the server to the latest version. Upgrade is done from the web interface of the server. This will ensure that the system has the latest features, bug fixes and security updates.
  
AMG 1 3 - Alarm Message 3 (8193) to group 1 (84)
 
RCO 5 ON – Turn on the relay that controls the lamp
 
  
AMG 1 0 – Alarm Message OFF to group 1 (84)
+
==Mounting & Dimensions==
RCO 5 OFF – Turn off the lamp
+
The cabinet should be mounted on a shelf or in a 19” rack. It contains one AMC-IP processor board only. The server includes a power board.
 +
<table style="max-width:80%; border-style: double; border-color: #c7c7c7;">
 +
<tr style="rowspan:2;">
 +
<td style="display: block; vertical-align: bottom;">[[Image:XE1FrontView.PNG|500px]]</td>
 +
</tr>
 +
<tr>
 +
<td style='background-color:#efefef;'>Front View</td>
 +
</tr>
 +
</table>
 +
<table style="max-width:80%; border-style: double; border-color: #c7c7c7;">
 +
<tr style="rowspan:2;">
 +
<td style="display: block; vertical-align: bottom;">[[Image:XE1RearView.PNG|500px]]</td>
 +
</tr>
 +
<tr>
 +
<td style='background-color:#efefef;'>Rear View</td>
 +
</tr>
 +
</table>
 +
<table style="max-width:80%; border-style: double; border-color: #c7c7c7;">
 +
<tr style="rowspan:2;">
 +
<td style="display: block; vertical-align: bottom;">[[Image:XE1TopView.PNG|500px]]</td>
 +
</tr>
 +
<tr>
 +
<td style='background-color:#efefef;'>Top View</td>
 +
</tr>
 +
</table>
  
'''Note:''' Multiple commands are separated by semicolon ( ; )
+
== Additional information ==
 +
===Remote Control Inputs and outputs ===
 +
The AlphaCom XE1 does not support any inputs or outputs on the server itself. A number of external devices can be used to provide inputs and outputs.
 +
* For inputs, see [[RCI - Remote Control Input in AlphaCom Systems]]
 +
* For outputs, see [[RCO_-_Remote_Control_Output|Remote Control Outputs]]
  
==Remote Control Outputs (RCO)==
+
===Specifications ===
XE1 does not support any RCO's in the server itself. If remote control outputs are required, please use [[TKIS-2|TKIS-2 kit]] or [[IP-ARIO]].
+
* [https://www.zenitel.com/product/alphacom-xe1 Additional Documentation on Zenitel.com]
 
 
=Factory Reset (coldstart)=
 
Performing a '''cold start''' of the AMC-IP board will delete all previous programming, load factory default settings and set the IP-address to 169.254.1.5 with mask 255.255.0.0 on Eth0.
 
 
 
===Cold start procedure===
 
[[Image:Cold Start of AMC-IP.jpg|right|200px|thumb|Cold start to load default factory settings]]
 
*Power on the XE1 server by inserting the power cable, while holding down the cold start button.
 
*Hold the [[AMC-IP#LED indicators|cold start button]] on the [[AMC-IP]] board depressed.
 
*Press the reset button on the [[APC]] card briefly. (On the E7 exchange, the reset button is located on the power card.)
 
*Keep the cold start button pressed at least 2 sec. after reset. The AMC status LED will blink green when the boot is ready.
 
 
 
<br/><br/>
 
=== Cold-start of AMC application only, keep IP setting ===
 
[[Image:Cold Start of AMC-IP.2.jpg|right|200px|thumb|Cold-start of AMC application]]
 
*Press the reset button on the APC card briefly. (On the E7 exchange, the reset button is located on the power card.)
 
*After 10 sec., press the cold start button on the AMC-IP board.
 
*Keep cold start button pressed until AMC running LED is blinking green.
 
><br/><br/>
 
 
 
== Modify Factory Default Settings ==
 
After cold start the system is set up with a default program and is working without any further programming. To change or add to the default settings, the [[AlphaPro]] programming tool must be used.
 
 
 
complete
 
uten ip
 
andre metoder
 
 
 
=Upgrade=
 
==Software upgrade==
 
=[http://www.zenitel.com/product/alphacom-xe1 Additional Documentation on Zenitel.com]=
 
  
[[Category:AlphaCom Servers]]
+
[[Category: AlphaCom Servers]]

Latest revision as of 13:20, 9 February 2023

XE1.PNG
AlphaCom XE1 Audio Server with HD Voice

Highlights

  • Made to provide critical communication in any environment
  • Supports 552 IP stations
  • Environmental friendly and energy saving - max. 4 W
  • SIM card based software configuration and disaster recovery
  • Fully compatible with any AlphaCom system

Connectors

XE1 eth serial.png


Power

The AlphaCom XE1 is powered by 5VDC from 90-240VAC power adapter. The power adapter comes with the XE1 server.

Network

The XE1 server has two RJ-45 ethernet ports for IP communication. Ethernet port 0 (Eth 0) is by default configured as a Management port, allowing connection to the embedded web server (AlphaWeb) and connection of the PC configuration tool AlphaPro. Default IP addresses:

  • Eth0 has IP address 169.254.1.5
  • Eth1 gets IP address from DHCP by default

Serial Ports

Serial ports XE1.PNG
XE1 Serial ports pinout

Serial ports can be used for communication with external equipment. There are two serial ports:

  • Serial Port 0: R232 on an 9-Pin D-sub connector
  • Serial Port 1: RS232, RS422 or RS485 on an RJ45 connector
    • RS232:: Switch 8 on S601 on the AMC-IP board must be set to OFF (default).
    • RS422: Switch 8 on S601 on the AMC-IP board must be set to ON. Jumpers J1 and J2 in position 1-2
    • RS485: Switch 8 on S601 on the AMC-IP board must be set to ON. Jumpers J1 and J2 in position 2-3 (default)

To access the jumpers J1 and J2, remove the top lid of the XE1 server:

SerialPortJumpers XE1.png
Jumpers J1 and J2 for selection of
RS422 or RS485 for Serial Port 1

Installation

  • Remove the front cover of the XE1 cabinet
  • Prepare the AMC-IP board with the STIC according to this article, then insert the AMC-IP board into the server. Give the board a firm final push to make sure it goes all the way into position.
OBS icon
  • Turn power off before inserting or removing the AMC-IP board


  • Insert the plug from the power adapter. Make sure that the cable goes underneath the strain relief.
  • Insert the power adapter to the mains socket.
  • Watch the LEDs of the AMC-IP board. The system uses approx. 70 seconds to start up. When running the green status LED should be flashing.
  • Connect a laptop to Eth 0 port, open a web browser (e.g. Firefox or Chrome), and log on to the web server using IP address 169.254.1.5. (Default Username/Password = admin/alphaadmin)
  • Upgrade the software of the server to the latest version. Upgrade is done from the web interface of the server. This will ensure that the system has the latest features, bug fixes and security updates.
  • Replace the front cover of the XE1 cabinet

Configuration

  • AlphaPro is the Windows application used for configuring the AlphaCom XE system. Configuration of user data, such as Directory Numbers, Direct Access Keys, Group Calls etc. is done from AlphaPro.
  • AlphaWeb is the embedded web server running on AlphaCom XE. The AlphaWeb server provides functions for system monitoring, system configuration, and system upgrade. Initial connection is done by connecting a laptop to Eth 0 port, open a web browser (e.g. Firefox or Chrome), and log on to the web server using IP address 169.254.1.5. (Default Username/Password = admin/alphaadmin).


Factory Reset (coldstart)

AMC-IP ColdStartButton.png
Cold start button on AMC-IP board


Cold start procedure

This procedure will delete all previous programming, load factory default settings and set the IP-address to 169.254.1.5 with mask 255.255.0.0 on Eth0.

  • Press and hold the cold start button on the AMC-IP board, then power up the XE1 server.
  • Keep the cold start button pressed for at least 2 seconds after power on, then release the button.
  • The AMC-IP status LED will flash green when the server is up and running

Cold-start of intercom application only, keep the IP settings

This procedure will delete all intercom configuration (i.e. delete all AlphaPro configuration), but keep all IP Settings (AlphaWeb configuration).

  • Power up the AlphaCom XE1 server
  • After 10 seconds, press and hold the cold start button on the AMC-IP board.
  • Keep the cold start button pressed until the AMC-IP status LED is flashing green.

Other methods of factory default

The server can be set to factory default values also:

  • From AlphaWeb: System Maintenance -> System Recovery -> Load Factory Defaults
  • From AlphaPro: Upload a default AlphaPro database to the exchange



Software upgrade

  • It is highly recommended to upgrade the software of the server to the latest version. Upgrade is done from the web interface of the server. This will ensure that the system has the latest features, bug fixes and security updates.


Mounting & Dimensions

The cabinet should be mounted on a shelf or in a 19” rack. It contains one AMC-IP processor board only. The server includes a power board.

XE1FrontView.PNG
Front View
XE1RearView.PNG
Rear View
XE1TopView.PNG
Top View

Additional information

Remote Control Inputs and outputs

The AlphaCom XE1 does not support any inputs or outputs on the server itself. A number of external devices can be used to provide inputs and outputs.

Specifications