The '''ELTSI-1 line end transponder''' ensures reliable monitoring of the loudspeaker lines. Where impedance measurements may result in an erroneous report of a broken line, the line end transponder will always report the correct health of the loudspeaker loop.
+
The '''ELTSI-1 line end transponder''' ensures reliable monitoring of the loudspeaker lines. Where impedance measurements may result in an erroneous report of a broken line, the line end transponder will always report the correct health of the loudspeaker line.
  
 
* Loudspeaker line end transponder
 
* Loudspeaker line end transponder
Line 8: Line 10:
  
 
Each amplifier can have a '''total of 10 LETs (ELTSI-1)''' divided among the channels.<br>
 
Each amplifier can have a '''total of 10 LETs (ELTSI-1)''' divided among the channels.<br>
Several ELTSI-1 on the same amplifier channel is making it possible to branch out the loudspeaker loops.
+
Several ELTSI-1 on the same amplifier channel is making it possible to branch out the loudspeaker lines.
  
  
Line 40: Line 42:
 
unit should be placed in such a way that the status indicator can be easily seen after installation. This will ease the maintenance of the system.
 
unit should be placed in such a way that the status indicator can be easily seen after installation. This will ease the maintenance of the system.
  
{{Warn}} ''The ELTSI-1 unit shall not be mounted in areas classified as Ex areas. If a line end transponder is''
+
{{Warn|The ELTSI-1 unit shall not be mounted in areas classified as Ex areas. If a line end transponder is required in such areas, it must be installed in a flame-proof enclosure (Ex d) according to IEC 60079. }}
          ''required in such areas, it must be installed in a flame-proof enclosure (Ex d) according to IEC 60079.''
 
  
 
=== Setting the Address ===
 
=== Setting the Address ===
Line 79: Line 80:
 
Complete the installation by securing the lid again, using the four lid retention screws.
 
Complete the installation by securing the lid again, using the four lid retention screws.
  
{{Warn}} '''''Tighten well but not more than 1.3Nm torque.'''''
+
{{Warn|Tighten well but not more than 1.3Nm torque. }}
  
 
=== Status Indication LED ===
 
=== Status Indication LED ===
 
When the device is connected and properly powered from the amplifier, it will periodically signal its status via the small green LED indicator. The LED indicator can flash in various patterns as follows:
 
When the device is connected and properly powered from the amplifier, it will periodically signal its status via the small green LED indicator. The LED indicator can flash in various patterns as follows:
  
<u>'''After Reset or Power-Up:'''</u> <br>
+
'''After Reset or Power-Up:''' <br>
 
3 short flashes every 10 seconds (sequence is repeated 2 or 3 times) followed by 1 long flash plus the numerical address of the unit in short flashes, e.g. 5 short flashes indicates that the unit has address number 5.<br>  
 
3 short flashes every 10 seconds (sequence is repeated 2 or 3 times) followed by 1 long flash plus the numerical address of the unit in short flashes, e.g. 5 short flashes indicates that the unit has address number 5.<br>  
 
This is repeated until the ELTSI-1 receives a request from the amplifier.
 
This is repeated until the ELTSI-1 receives a request from the amplifier.
  
<u>'''After Contact with Amplifier:'''</u> <br>
+
'''After Contact with Amplifier:''' <br>
 
1 short flash every 10 seconds. The amplifier will send a new request to the ELTSI-1 circa every 15 seconds. If the request from the amplifier is not received within 60-70 seconds, the LED will emit 2 short flashes every 10 seconds followed by 1 long flash plus the numerical address of the unit in short flashes.<br>  
 
1 short flash every 10 seconds. The amplifier will send a new request to the ELTSI-1 circa every 15 seconds. If the request from the amplifier is not received within 60-70 seconds, the LED will emit 2 short flashes every 10 seconds followed by 1 long flash plus the numerical address of the unit in short flashes.<br>  
 
This is repeated until the ELTSI-1 receives a request from the amplifier.
 
This is repeated until the ELTSI-1 receives a request from the amplifier.
Line 96: Line 97:
 
== Additional Documentation ==
 
== Additional Documentation ==
 
For more documentation, please visit the Zenitel web page: https://www.zenitel.com/product/eltsi-1
 
For more documentation, please visit the Zenitel web page: https://www.zenitel.com/product/eltsi-1
 
[[Category:Public Address - Network amplifiers]]
 

Latest revision as of 12:59, 13 June 2024

Obsolete icon This product is discontinued!


ELTSI-1.
ELTSI-1

The ELTSI-1 line end transponder ensures reliable monitoring of the loudspeaker lines. Where impedance measurements may result in an erroneous report of a broken line, the line end transponder will always report the correct health of the loudspeaker line.

  • Loudspeaker line end transponder
  • Powered from and communicates over the loudspeaker lines
  • Small and simple to install
  • Rugged and weatherproof housing

Each amplifier can have a total of 10 LETs (ELTSI-1) divided among the channels.
Several ELTSI-1 on the same amplifier channel is making it possible to branch out the loudspeaker lines.


Installation

Overview

ELTSI-1


1 Cable Gland
2 Lid Retention Screw
3 Transparent Lid
4 Status Indicator LED
5 Address Selector
6 Connection Terminals
7 Cable Gland Entry
8 Mounting Holes



Placement

The ELTSI-1 Line End Transponder is a rugged device, intended for use in rugged environments. It can therefore be mounted in protected areas, or exposed areas with heavy rain and pollutants. The unit should be placed in such a way that the status indicator can be easily seen after installation. This will ease the maintenance of the system.

Warning icon The ELTSI-1 unit shall not be mounted in areas classified as Ex areas. If a line end transponder is required in such areas, it must be installed in a flame-proof enclosure (Ex d) according to IEC 60079.


Setting the Address

The address of the unit should be set before mounting as this will make the operation easier. The address is set using the address selector.

  • Remove the lid by carefully unscrewing the four lid retention screws.
  • Use a small screwdriver to turn the address selector (small arrow on the wheel) to a number between 1 and 10. The address of the unit shall be set according to the system plan.

Connecting the Terminals

If the cable entry is still covered, screw in the cable gland body until it punches the cover out to make a hole for cable access.

  • Thread the cable through the cable gland and cable entry of the unit.
  • Connect the loudspeaker line to either of the two spring loaded connection terminals.
EBMDR-8


1 Cable Line
2 Cable Gland
3 Cable Entry
4 Address Selector
5 Connection Terminals



Mounting

The ELTSI-1 unit must be mounted on a flat surface using the four screw holes. These holes are located under the lid retention screws.

If the unit is mounted inline, an extra cable gland must be mounted for the extending cable. When mounting inline, make sure to be consistent when connecting the cable to the terminals.

The screws used to mount the unit must be suitable for the purpose, and have a head diameter of not more than 6.6 mm. The diameter of the screw itself must be not be more than 4 mm. The ELTSI-1 box will “consume” 7 mm of the screw’s length. Depending on the type of material on which the device is mounted, use an M3.5 socket/slotted screw or a pan head wood screw of diameter 3.5 mm.

Complete the installation by securing the lid again, using the four lid retention screws.

Warning icon Tighten well but not more than 1.3Nm torque.


Status Indication LED

When the device is connected and properly powered from the amplifier, it will periodically signal its status via the small green LED indicator. The LED indicator can flash in various patterns as follows:

After Reset or Power-Up:
3 short flashes every 10 seconds (sequence is repeated 2 or 3 times) followed by 1 long flash plus the numerical address of the unit in short flashes, e.g. 5 short flashes indicates that the unit has address number 5.
This is repeated until the ELTSI-1 receives a request from the amplifier.

After Contact with Amplifier:
1 short flash every 10 seconds. The amplifier will send a new request to the ELTSI-1 circa every 15 seconds. If the request from the amplifier is not received within 60-70 seconds, the LED will emit 2 short flashes every 10 seconds followed by 1 long flash plus the numerical address of the unit in short flashes.
This is repeated until the ELTSI-1 receives a request from the amplifier.

Note icon Use of LET units must be enabled in EMT before the ELTSI-1 becomes active and the output must be calibrated successfully.