Dimensions (WxHxD) | Weight | |
TKIE-1 | 65 x 100 x 25 mm | 0.1 kg |
TKIE-2 | 74 x 106 x 30 mm | 0.2 kg |
TFIE/TFIX Extended Station Dimensions
Mounting the unit
Preparation for Drilling
The four mounting holes in the onwall box are Ø6.4 mm. Distance: 298 x 130 mm. Size of hole to be drilled depends on whether it is wall or column mounting:
Location
Make sure there is a clearance of minimum 230 mm on the left for frame movement.
Mounting Plate or Column
Fix the unit to mounting plate or column with 4 screws that fit the 4 screw holes in each corner of on-wall box (6.4 mm diameter). Use M5 x 20 or 25 with Philips head DIN7985 or Torx. Head diameter: 10 mm.
Wall
Fix the unit to the wall with 4 screws that fit the 4 screw holes in each corner of the on-wall box (6.4 mm diameter). Use Panhead – DIN7981 screw for plug or wooden wall. Head diameter: 10.8 B5.5 x 38 or 45 mm.
Mounting Cable Gland
Remove two blind plugs and insert one M16 and one M20 cable glands. Make sure to tighten sufficiently to attain IP66 rating for watertightness but be aware of plastic material limitations.
In order to ensure the required minimum degree of protection, the cable glands must be tightened securely.
Over-tightening can impair the degree of protection and damage the unit.
When tightening the cap nut of a cable gland, a suitable tool shall be used to prevent the gland from twisting.
Fastening Front Frame
Do NOT use more than 2.5 Nm torque when fastening the 12 screws into the front frame.