IP Heavy Duty - Restore Factory Defaults
From Zenitel Wiki
This procedure is applicable for the IP Heavy Duty station 1008072xx0
The unit can be set to use either Static IP or DHCP. On the rear side of the PCB there is a red status LED. You won’t be able to see the actual LED, but you can see the red light from it. Pay attention to this LED during the restore procedure:
Restore with Static IP
- Connect a push button (KEY1) between pin 1 and 4 on the P4 connector.
- While pressing the button, power up the station and keep the button pressed.
- Release the button after exactly 2 flashes of the LED.
- Let the LED flash for exactly 2 more times (Static IP) or exactly 4 more times (DHCP), then press the button again.
- Keep the button pressed until the LED flashes fast 2 times (Static IP) or flashes fast 4 times (DHCP) indicating a successful reset.
- Release the button and the station will restart with the factory default settings.
Factory default values:
- Station Mode: Pulse
- Station IP address: 169.254.1.100 or DHCP
- Username: admin
- Password: alphaadmin
Restore with Activated DHCP
The DHCP option is available from software version 01.07.
- While pressing the button, power up the station kit.
- When the station kit LED starts blinking, release the button after exactly 2 blinks.
- Let the LED blink for exactly 4 more times, then press the button again.
- Keep the button pressed until the LED blinks fast 4 times indicating a successful reset with activated DHCP.
- Release the button and the station kit will restart with the factory default settings.
Factory default values:
- Station Mode: Pulse
- Station IP address: From DHCP server
- Username: admin
- Password: alphaadmin