Actions

Anti-nuisance control (Event Handler)

From Zenitel Wiki

Revision as of 23:34, 8 October 2007 by Asle (talk) (New page: Anti-nuisance control Local Guard should be able to disable calls from substation for a periode of time. In the programming example below the guard station dials 9535 + substation number...)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)

Anti-nuisance control

Local Guard should be able to disable calls from substation for a periode of time.

In the programming example below the guard station dials 9535 + substation number to

disable calls from that station for 15 minutes.

Directory number 9535 is a two-step event trigger, feature 95/0. When dialled, an event

type 25 is triggered and the action string $SSC L%2.dir U2 moves the station to COS 2.

COS 2 is by default empty, which will prevent calls to be initiated. Also a 15 minute

timer is started, $ST L%2.dir W9000 L9999. The timer will trigger event type 21 When

timing out, and command $SSC L%2.dir U1 will move the station back to COS 1.

Event 1:

Event Owner: The guard station Event type: 25 - Event trigger with parameter Subevent: 0 When change to: ON When Related To: All Action: $SSC L%2.dir U2 $ST L%2.dir W9000 L9999

Event 2:

Event Owner: Station w. UDP, Id: 8 (all stations) Event type: 21 - Event timeout Subevent: 0 When change to: ON When Related To: Directory number 0 | 9999 Action: $SSC L%2.dir U1