VS-OPC UA for AlphaCom - Release Notes

From Zenitel Wiki

Revision as of 14:31, 28 February 2022 by EMortensen (talk | contribs)
AlphaCom icon 300px.png

Release State: Released
Release Version: 1.0.3.11
Installation Package: VS-OPC UA for AlphaCom_Setup_V1.0.3.11.msi

VS-OPC UA for AlphaCom 1.0.3.11

The AlphaNet OPC Server does not support configuring an event as a ”Condition”-event. Only “Simple” and “No-Event” are supported. The possibility of configuring “Condition” event has been removed for the AlphaOPCConfigurator application.

VS-OPC UA for AlphaCom 1.0.3.10

This release solves the issue, that the OPC-Server was not able to reconnect to the ICX-AlphaCom / ICX-core after a link disconnection. The OPC-Server will now constantly try reconnecting after a link disconnection.

VS-OPC UA for AlphaCom 1.0.3.9

In this release the following has been changed:

  • LineState typecasted to Byte. Parameter1 typecasted to Int32.
  • Attempt to use group message 0 is ignored and not transfered to ICX-AlphaCom.

VS-OPC UA for AlphaCom 1.0.3.8

MTN-2849: ICX-AlphaCom VS-SDK unstable 'related station' handling.

The ’related station’-field for an established connection is cleared in case another station calls one of the participants – gets busy and hangs up. This issue is now fixed.

VS-OPC UA for AlphaCom 1.0.3.7

The VS-OPC UA have been improved by

1)   ss.Linestate and cp.Parameter1 is typecasted to UInt32 as the protocol expects

VS-OPC UA for AlphaCom 1.0.3.6

The VS-OPC UA have been improved by

1)  Making VS-OPC UA Server able to connect to the the AlphaCom via a remote connection provided by the AlphaNetServiceProvider.

2) Updating the AlphaOPCConfigurator configuration utility for configuration of the remote connection.

VS-OPC UA for AlphaCom 1.0.3.5

When the connection from the OPC-server to the AlphaCom fails  and comes back again (either AlphaCom switch off/on, or Ethernet cable unplugged/plugged in again), the OPC-server seems unable to re-establish the link to AlphaCom.

This problem has now been fixed.

Shutdown of OPC-Server in case of no connection to AlphaCom  during startup has been changed.

The server will now constantly try reconnecting to Alphacom until connection is established or the server is manually closed down.

VS-OPC UA for AlphaCom 1.0.3.4

OPC-UA service does not start automatically A new batch file will install the OPC_UA service as AlphaCom_OPC. The service will run permanently.

VS-OPC UA for AlphaCom 1.0.3.3

Update COS from the OPC-client

A new station item 'station_cos' has been added. This can be used to set a new COS value for the station.

VS-OPC UA for AlphaCom 1.0.3.2

MTN-1832: cr_iterate_command & cr_iterate_station does not match station display

The order of the call requests in the queue as held by the OPC-server did not always match the order as shown in the station display. This has now been rectified.

VS-OPC UA for AlphaCom 1.0.3.1

First release, functionality is the same as VS-OPC Classic for AlphaCom_Setup_V6.0.3.2