Difference between revisions of "IP-ARIO"
From Zenitel Wiki
(→PA Failure State System) |
|||
Line 1: | Line 1: | ||
+ | |||
==PA Failure State System== | ==PA Failure State System== | ||
Line 154: | Line 155: | ||
|} | |} | ||
+ | |||
+ | ===Updated Event Handler Macros and $DP messages=== | ||
+ | [[wudd]] (Added label and string variables) | ||
+ | [[%udd]] (Added label and string variables) | ||
+ | [[IND_-_Indicator_control_for_CRMIV_LEDs,_buzzer_etc. |gind]] (NEW group version of ''ind'') | ||
+ | [[%paf]] (NEW, PA fault in UDP group check) | ||
+ | [[%pai]] (NEW, PA fault indicator in DAK block) | ||
+ | [[%pap]] (NEW, PA fault mail priority) | ||
+ | [[%prci]] (NEW, Current Physical RCI state) | ||
+ | [[%prco]] (NEW, Current Physical RCO state) | ||
+ | |||
+ | $[[PA_CMD]] (NEW, PA command, ACK/CLEAR) | ||
+ | $[[SET_IPRCO]] (NEW, Set physical RCO on IP station/IP-ARIO) | ||
+ | $[[CANCEL_MAIL]](Added option for delete mail with specific priority, Mail-id = 253) | ||
+ | |||
Revision as of 08:13, 6 July 2011
PA Failure State System
When used as PA interface some of the IP-ARIO inputs are used for reporting failure state of 1 or 2 amplifiers.
The various IP-ARIO PA faults and states are reported as sub events on the line error event.
When fault state is reported OFF from IP-ARIO the fault state in AMCD will still be active until acknowledge and cleared by the user.
A NVRAM structure is used for additional configurable elements.
Configurable elements are:
- Default description text intended for use in fault mail to PA panels. The text are sent to event handler as %2.nam
- Default placement of status indication in the "DAK block" related to the PA interface. ( DAK block)
- Default priority used for fault mails. (Unique priority make it easy to remove specific fault from mail queues)
Event Handler IP-ARIO failure states | ||||||
---|---|---|---|---|---|---|
Event text (%2.nam) | SUB event (%sev) | DAK block index (%pai) | Priority (%pap) | Comment | ||
FAULT ACK | 2 | 7 | 50 | Event text for debugging | ||
FAULT CLEAR | 3 | 10 | 50 | Event text for debugging | ||
ZONE BLINK | 4 | 1 | 50 | Event text for debugging | ||
ZONE STEADY | 5 | 1 | 50 | Event text for debugging | ||
IPA DOWN | 10 | 4 | 140 | |||
RELAY 1 | 11 | 2 | 100 | |||
POWER 1 | 12 | 5 | 101 | |||
LINE MON 1 | 13 | 8 | 102 | |||
XLR MON 1 | 14 | 11 | 103 | |||
RELAY 2 | 15 | 3 | 104 | |||
POWER 2 | 16 | 6 | 105 | |||
LINE MON 2 | 17 | 9 | 106 | |||
XLR MON 2 | 18 | 12 | 107 | |||
- | 20 | - | - | "Live" State of Line Mon. 1 | ||
- | 21 | - | - | "Live" State of Line Mon. 2 | ||
- | 22 | - | - | "Live" State of Amp 1 Discon. | ||
- | 23 | - | - | "Live" State of Amp 2 Discon. | ||
- | 24 | - | - | "Live" State of 20KHZ Mon. 1 | ||
- | 25 | - | - | "Live" State of 20KHZ Mon. 2 | ||
- | 26 | - | - | "Live" State of Level Detect. 1 | ||
- | 27 | - | - | "Live" State of Level Detect. 2 |
Updated Event Handler Macros and $DP messages
wudd (Added label and string variables) %udd (Added label and string variables) gind (NEW group version of ind) %paf (NEW, PA fault in UDP group check) %pai (NEW, PA fault indicator in DAK block) %pap (NEW, PA fault mail priority) %prci (NEW, Current Physical RCI state) %prco (NEW, Current Physical RCO state)
$PA_CMD (NEW, PA command, ACK/CLEAR) $SET_IPRCO (NEW, Set physical RCO on IP station/IP-ARIO) $CANCEL_MAIL(Added option for delete mail with specific priority, Mail-id = 253)
Default Grouping of fault state on CRM DAK
The status of faults of one IP-ARIO are grouped to one CRM DAK block of 3 * 4 DAK keys.
Fault Indication On DAK panel | ||||||
---|---|---|---|---|---|---|
ZONE FAULT | RELAY 1 | RELAY 2 | ||||
IPA DOWN | POWER 1 | POWER 2 | ||||
FAULT ACK | LINE MON 1 | LINE MON 2 | ||||
FAULT CLEAR | XLR DISCON 1 | XLR DISCON 2 |