Relay 5 to 8 has a corresponding output selector switch. With this switch one can select if the Contact Set #1 should provide dry contacts, or if it should forward power from the power forwarding connector. Contact Set #2 will always provide dry contacts, regardless of the position of the output selector switch.  
 
Relay 5 to 8 has a corresponding output selector switch. With this switch one can select if the Contact Set #1 should provide dry contacts, or if it should forward power from the power forwarding connector. Contact Set #2 will always provide dry contacts, regardless of the position of the output selector switch.  
* '''Left position''': The input requires an active signal, typically 5, 12V or 24VDC. The input is galvanic isolated with an opto-coupler. Polarity as indicated on the drawing.
+
* '''Left position''': Contact Set #1 provides dry contacts.  
* '''Right position''': The input requires a dry contact
+
* '''Right position''': Contact Set #1 provides power. It requires that a power supply is connected to the IP-LCM unit.
  
 
'''Relay contact ratings''':
 
'''Relay contact ratings''':

Revision as of 15:05, 10 January 2019

IP-LCM connectors

Inputs

There are 8 inputs. Each of them has a corresponding selector switch, with which one can select between a dry closing contact or an active input.

  • Left position: The input requires an active signal, typically 5, 12V or 24VDC. The input is galvanic isolated with an opto-coupler. Polarity as indicated on the drawing.
  • Right position: The input requires a dry contact

Outputs

There are 8 relays, each with two sets of changeover contacts (DPDT). The contact terminals, Normally Open (NO), Normally Closed (NC) and Common (COM), are labeled in the silk print of the PCB.

IP-LCM relays


Relay 5 to 8 has a corresponding output selector switch. With this switch one can select if the Contact Set #1 should provide dry contacts, or if it should forward power from the power forwarding connector. Contact Set #2 will always provide dry contacts, regardless of the position of the output selector switch.

  • Left position: Contact Set #1 provides dry contacts.
  • Right position: Contact Set #1 provides power. It requires that a power supply is connected to the IP-LCM unit.

Relay contact ratings:

  • Outputs: DPDT (Double Pole Double Throw). NO (Normal Open), NC (Normal Closed), COM (Common)
  • Switched voltage: < 250VAC Rated (400VAC Max)
  • Switched Voltage: < 2000 VA max
  • Switching Current: < 8A rated (15A max, 4s)

Indicators

Each output has a LED which indicates if the output is active or not.