Solution
Alarm Message Distribution (AMG):
- The fire alarm system provides a relay contact that closes when the fire alarm is activated. This contact should be connected to RCI 1 and start a prerecorded Fire Alarm Message to all stations.
- The Fire Alarm Message should stop when the relay contact opens.
Mail To Station (MST):
- A temperature alarm is connected to RCI 2. When the contact closes, a text message saying "Temp alarm" should be sent to the "Reception".