Exigo 1.7 Release Notes
From Zenitel Wiki
Exigo 1.7.3.6
Release status: Official, available Release date: 27.05.2025 Software collection file: EXIGO-1.7.3.6.zip
Software included in EXIGO-1.7.3.6.zip
| Product | Version | Product description |
| VSF-Turbine | VSFT-PA.6.5.3.10 | Firmware for devices. |
| VSFX | 1.3.3.3 | Firmware for ICX-500 PSC |
| AlphaSys Firmware | 13.0.3.17 | Firmware for the ESC1 (Primary System Controller/AMC-IP board) alpha-sys_13.0.3.16.apkg, bsp_32.2.3.6.apkg |
| VS-EMT Exigo Management Tools | EMT-1.7.3.5 | Configuration tool, installed on a Windows PC |
| VS-DEVICE-MIB | 202203070000Z | SNMP MIB for Exigo EXI-Devices, for upload in 3rd-party SNMP based monitoring tools |
New Feature
None
Enhancements and Fixed Issues
MTN-4711 Panel reboots when audio program is toggled
Fixed initialization of audio resampler and HD audio program feed to panels
MTN-4710 SNMP Traps don’t send cleared state
Traps will now report cleared fault state
MTN-4695 Controller reboot issue
Fixed an issue where interrupting a looping announcement with a new announcement would cause controller reboot
MTN-4646 Activity indicator not working on live speech
Fixed issue with live speech activity indication on panel doing the announcement
MTN-4645 System status Green LED not showing system connected
System status is correctly reported now by configured panel key green LED
MTN-4489 Fixed issue with ICX multicast interface setup after cold boot
ICX will no longer use stations for multicast relay if not configured so
MTN-4303 Faults cannot be cleared after affected device change
Fixed that faults with source state unknown can be cleared
Known Issues
MTN-4429 Sound degradation with multiple programs on same amplifier
Exigo 1.7.3.5
Release status: Unreleased version Release date: 21.11.2024 Software collection file: EXIGO-1.7.3.5.zip
Software included in EXIGO-1.7.3.5.zip
| Product | Version | Product description |
| VSF-Turbine | VSFT-PA.6.5.3.9 | Firmware for devices. |
| VSFX | 1.3.3.2 | Firmware for ICX-500 PSC |
| AlphaSys Firmware | 13.0.3.16 | Firmware for the ESC1 (Primary System Controller/AMC-IP board) alpha-sys_13.0.3.16.apkg, bsp_32.2.3.6.apkg |
| VS-EMT Exigo Management Tools | EMT-1.7.3.5 | Configuration tool, installed on a Windows PC |
| VS-DEVICE-MIB | 202203070000Z | SNMP MIB for Exigo EXI-Devices, for upload in 3rd-party SNMP based monitoring tools |
New Feature
None
Enhancements and Fixed Issues
MTN-4559 No uncontrolled LED blinking in panels after sw-optimization
Fixed issue with panel LED on status and handling causing LEDs starting to blink after several weeks
MTN-4532 Update OpenSSH version and other relevant libraries
MTN-4459 EAPFX-6-V2 Microphone monitoring now working
Fixed reading of internal and external mic monitoring status
MTN-4456 Recovery OS now working on all IP-LCM devices
Added IP-LCM rev.0201 support to Recovery OS
MTN-4453 EMT Audio Activity list now showing all actual activities
Previously when activity divided into multiple zones was present, some activities were missing in Activity List. This is now fixed.
MTN-4452 During system power cycle all sub directory numbers are now registered
Devices with multiple sub directory numbers will register each instance with a small delay
MTN-4448 IP-LCM no longer stuck in reboot loop after updating to PA software
Add support for latest IP-LCM HW revision to PA software
MTN-4428 Maximum of 30 messages can be started in parallel
Increased number of maximum parallel wav player resources from 8 to 30 (this includes chimes)
MTN-4427 ICX-500 Log web page now working
Fixed log print web page session
MTN-4400 Devices can now be upgraded from PA only to non PA software
Fixed upgrade file check for PA and non PA software
MTN-4399 EAPFX V2 stations now shows name in WEB information page
Added EAPFX V2 stations to PA software WEB config name list
MTN-4390 ENA2 AC2 amplifiers no longer accept old unsupported software versions
Disabled downgrade of software to older unsupported versions
MTN-4380 Increased gain for recall and gong in Exigo mode
Difference in audio level for messages, recall, direct speech, and chimes when using AMC-IP and ICX as Exigo Controller
MTN-4370 Redundant system controller now reports as error when missing
Added system error message for missing redundant system controller
MTN-4322 Modbus now working with ICX-500 as controller
Modbus could not be triggered with ICX as Exigo Controller - this is now fixed
MTN-4306 EMT monitoring no longer crashes during connection to controller
Connection to controller in EMT monitoring was causing EMT crash in some scenarios. This is now fixed.
MTN-4305 Missing debounce time now correctly applied
Missing device debounce time set in EMT was not correctly applied in the system
MTN-4304 ENA amplifiers now applies EMT volume control
Local WEB config profile is correctly cleared if overridden by EMT
MTN-4302 EMT monitoring no longer shows call records that are not active in the system
Call records that are not active in the system are not showing up in EMT. It was previously occurring in A/B systems after EMT reconnected to controller.
MTN-4301 Increased Control output speed to avoid too slow reactions on activity change
Speed up CO activity processing, system with very high number of activities can still act slower
MTN-4300 Improved audio quality after program interrupt
Fix issue with bad audio quality first few seconds after live speech ends when ESC1 is used as multicast forwarder by ICX
MTN-4299 Chime sound no longer interrupted in A/B systems with high load
Fix issue when ESC1 is used as multicast forwarder by ICX
MTN-4297 Increased ECPIR panel response in systems with high activity load
Optimized panel LED and activity handling, still on very high system activity load panel can act little bit slower
MTN-4280 Amplifiers in an Exigo system no longer breaks audio streams priority
Fixed so that audio streams priority works as following:
If A/B controller is sending audio streams with different priories:
VOICE streams (live speech, message, alarm) are always higher priority than MUSIC (program) streams if 2 VOICE streams are received where B has higher priority than A they will be mixed if 2 MUSIC streams are received where B has higher priority than A, B will play If both controllers are sending same priority audio stream, A will play
MTN-4271 Fixed issue with all zones not included in ExigoNet
Exigo with ICX as controller was unable to receive two different zones on a SIP call - is now fixed
MTN-4258 EMT - Possible to assign Flowires to both A and B systems
Flowires were previously automatically assigned to A system, now they can be assigned to both systems.
MTN-4112 Backup control in EMT now showing amplifiers for take over and/or release
This is fixed so that every time user clicks on amplifier, this list is populated again.
Known Issues
MTN-4429 Two different audio programs played on same amplifier can cause temporary sound degradation
Exigo 1.7.3.4
Release status: Unreleased version Release date: 09.02.2024 Software collection file: EXIGO-1.7.3.4.zip
Software included in EXIGO-1.7.3.4.zip
| Product | Version | Product description |
| VSF-Turbine | VSFT-PA.6.5.3.8 | Firmware for devices. |
| VSFX | 1.3.3.0 | Firmware for ICX-500 PSC |
| AlphaSys Firmware | 13.0.3.16 | Firmware for the ESC1 (Primary System Controller/AMC-IP board) alpha-sys_13.0.3.16.apkg, bsp_32.2.3.6.apkg |
| VS-EMT Exigo Management Tools | EMT-1.7.3.2 | Configuration tool, installed on a Windows PC |
| VS-DEVICE-MIB | 202203070000Z | SNMP MIB for Exigo EXI-Devices, for upload in 3rd-party SNMP based monitoring tools |
New Feature
None
Enhancements and Fixed Issues
MTN-4272 ICX as PSC (Primary System Controller) a sweeping noise on recall could occur
Removed occurrence of a sweeping noise when using recall function.
MTN-4268 ENA2100-AC channel shutdown error message handling updated
When ENA2100-AC channel shutdown error has disappeared, error message can now be removed.
MTN-4267 ICX as PSC (Primary System Controller), message of missing PSC (PSC error) did not disappear after reconnecting
After a LAN disconnection of ICX, message of missing PSC (PSC error) in ESC1 GUI and Amplifier Web kept message despite ICX reconnection and operating. Updated to avoid faulty messages.
MTN-4248 Broadcasting of Live speech and Recall recordings appeared with different levels on output
Adjusted audio levels of the two types of broadcasting to be outputted equally.
MTN-4235 ICX as PSC (Primary System Controller) the FCDC3 were not reported missing after being disconnected second time and Device Report timing were faulty
FCDC3 reported missing is now working after second time being disconnected and Missing Device Report is generated in less than 15 seconds.
MTN-4090 Line fault LED takes long time to indicate for a detected fault
Line fault LED now reacts immediately when fault is detected.
Known Issues
MTN-4429 Sound degradation with multiple programs on same amplifier
Exigo 1.7.3.3
Release status: Unreleased version Release date: 18.01.2024 Software collection file: EXIGO-1.7.3.3.zip
Software included in EXIGO-1.7.3.3.zip
| Product | Version | Product description |
| VSF-Turbine | VSFT-PA.6.5.3.8 | Firmware for devices. |
| VSFX | 1.2.3.7 | Firmware for ICX-500 PSC |
| AlphaSys Firmware | 13.0.3.16 | Firmware for the ESC1 (Primary System Controller/AMC-IP board) alpha-sys_13.0.3.16.apkg, bsp_32.2.3.6.apkg |
| VS-EMT Exigo Management Tools | EMT-1.7.3.2 | Configuration tool, installed on a Windows PC |
| VS-DEVICE-MIB | 202203070000Z | SNMP MIB for Exigo EXI-Devices, for upload in 3rd-party SNMP based monitoring tools |
New Feature
None
Enhancements and Fixed Issues
MTN-4255 Speaker Line Monitoring (SLM) stopped working after amplifier power cycle
In rare cases SLM was not working after power cycle due to missing pilot tone. Updated to ensure working SLM monitoring.
MTN-4253
MTN-4252 ENA2x00-AC2 amplifiers could report faults during planned shutdown
Amplifiers could report “Low Voltage Alert” from internal voltage monitoring during shutdown of amplifier. Updated to not report this faults when it is due to shutdown of amplifier.
MTN-4251 Ground fault LED (Gnd) not indicating properly in case only Channel 1 has Ground fault
Ground fault LED updated to take into account faults on both channels and now indicating correctly under all circumstances.
MTN-4242 Speaker Line Monitoring (SLM) calibration and configuration data reset after power cycle
SLM calibration and configuration could get corrupted and reset if amplifier was powered off when configuration file was being written. Configuration file is now only written during calibration and on amplifier power up. Note: Changing Insulation resistance trigger lever from default 100k ohm is only provided for trained service personnel.
MTN-4089 Amplifier reboots if manual Speaker Line Monitoring (SLM) measurements was done too early after power up
SLM parameters are now read immediately on application boot to avoid this behavior.
MTN-4084 TKIS-2 (Amplifier P-1670 mode): Start-up failure
A bad timing combination could cause amplifier mode to not be valid. This has been updated and corrected to avoid.
MTN-4083 TKIS-2 (Amplifier P-1670 mode): Status input monitoring
Status inputs (Line fault, Ground fault, Amplifier fault) for TKIS-2 in amplifier P-1670 mode was not always acting correctly. Updated for correct monitoring of amplifier status.
Known Issues
MTN-4429 Sound degradation with multiple programs on same amplifier
Exigo 1.7.3.2
Release status: Official, available Release date: 26.04.2023 Software collection file: EXIGO-1.7.3.2.zip
Software included in EXIGO-1.7.3.2.zip
| Product | Version | Product description |
| VSF-Turbine | VSFT-PA.6.5.3.6 | Firmware for the following devices: ESC1 (Secondary System Controller), ENA2100-AC, ENA2200, ENA2200-AC2, ENA2400-AC, ENA2400-AC2, ENA2400-DC, 1670, EAPIR-8, ECPIR-P, ECPIR-3P, EBMDR-8, EAPFX-1, EAPFX-1-V2, EAPFX-6, EAPFX-6-V2, EAPII-1, EAPII-6, AVC Source Device, IP Speaker, TKIS-2, TKIE-2, IP-LCM, TA-10. |
| VSFX | 1.2.3.7 | Firmware for ICX-500 PSC |
| AlphaSys Firmware | 13.0.3.16 | Firmware for the ESC1 (Primary System Controller/AMC-IP board) alpha-sys_13.0.3.16.apkg, bsp_32.2.3.6.apkg |
| VS-EMT Exigo Management Tools | EMT-1.7.3.2 | Configuration tool, installed on a Windows PC |
| VS-DEVICE-MIB | 202203070000Z | SNMP MIB for Exigo EXI-Devices, for upload in 3rd-party SNMP based monitoring tools |
New Feature
None
Enhancements and Fixed Issues
MTN-4066 ENA2x00-AC2: Improved speaker line monitoring (SLM) on long speaker lines
The speaker line monitoring (SLM) measurements on long speaker lines (technical perspective up to 800nF) have been improved.
MTN-3987 ENA2x00-AC2: Adjustable ground fault limit
Detection limit can be set from terminal. Default is 100kohm.
MTN-3982 ENA2x00-AC2: Removed occurrence of false ground fault detection
During calibration of systems with long speaker lines, detection of false ground fault could occur. This would again prevent the calibration of the speaker lines. The occurrence of false ground faults is no longer present.
Known Issues
None
Exigo 1.7.3.0
Release status: Official, available Release date: 13.12.2022 Software collection file: EXIGO-1.7.3.0.zip
Software included in EXIGO-1.7.3.0.zip
| Product | Version | Product description |
| VSF-Turbine | VSFT-PA.6.5.3.5 | Firmware for the following devices: ESC1 (Secondary System Controller), ENA2100-AC, ENA2200, ENA2200-AC2, ENA2400-AC, ENA2400-AC2, ENA2400-DC, 1670, EAPIR-8, ECPIR-P, ECPIR-3P, EBMDR-8, EAPFX-1, EAPFX-1-V2, EAPFX-6, EAPFX-6-V2, EAPII-1, EAPII-6, AVC Source Device, IP Speaker, TKIS-2, TKIE-2, IP-LCM, TA-10. |
| VSFX | 1.2.3.7 | Firmware for ICX-500 PSC |
| AlphaSys Firmware | 13.0.3.16 | Firmware for the ESC1 (Primary System Controller/AMC-IP board) alpha-sys_13.0.3.16.apkg, bsp_32.2.3.6.apkg |
| VS-EMT Exigo Management Tools | EMT-1.7.3.2 | Configuration tool, installed on a Windows PC |
| VS-DEVICE-MIB | 202203070000Z | SNMP MIB for Exigo EXI-Devices, for upload in 3rd-party SNMP based monitoring tools |
New Feature
EPB-499 Exigo Controller updated to use ICX-500 as PSC
Exigo Controller ESC1 updated to use ICX-500 as Primary System Controller (PSC). Current PSC named AMC-IP shall not be installed at same time.
When using the ICX-500 as PSC this is mounted next to the ESC1. The ICX-500 may either be installed in a 1HU shelf for ICX-500 or mounting bracket for ICX-500. The ICX-500 will be interconnected with the ESC1 via Ethernet cable. From ICX-500 Eth1 connects to ESC1 Eth2. AB systems shall not mix type of PSC in the two Exigo Controllers present. In Exigo Management Tool (EMT) no differences will appear regardless of type of PSC used.
Important: ICX-500 works as the Primary System Controller (PSC) in an Exigo Controller (ESC1) from firmware version vsfx-1.2.3.7.
Enhancements and Fixed Issues
MTN-3989 EMT works when pushing ack all on single systems
In monitoring, the ack all button was causing EMT to crash. This is now solved.
MTN-3988 A failing LET can now be reported as a fault
Before the failing LET would always be reported as a warning independent on what was selected in EMT. This has now been fixed.
MTN-3968 EX panels V2 no longer give fault message: "ETH1 is disconnected"
EX panels do not have Ethernet ports so there is no Ethernet monitoring
MTN-3965 Backup amplifier will check for PSC connectivity
Backup amplifier will ping PSC(s) before taking over any amplifier to make sure that it has connectivity to at least one PSC (Primary System Controller).
MTN-3960 Update of settings on the main web page are now properly applied when saved
When changes are being saved on the main settings' web page, they will be applied and the device will automatically reboot. Earlier you were offered the options to reboot or returning back, which could cause erratic behaviour.
MTN-3945 Enabling configuration option for SLM and LET monitoring at the same time
SLM and LET monitoring can now be enabled on amplifiers except ENA2-AC2.
MTN-3844 X-IGO SIP Header Issue fixed
Fixed an issue that caused the controller to reset if an X-IGO SIP header was used from an external integration while a call was active.
MTN-3807 Removed Channel 2 from configuration view when in bridge mode
In bridge mode (one channel mode) audio Channel 2 is not be visible in view for ENA2X00-AC2 amplifiers anymore.
MTN-3806 Speech sound no longer lost on A/B system takeover
When making configuration changes on GUI, the device gets into a state where speech sound gets lost if A-system (ESC1) loses connection.
MTN-3755 AVC source now has same volume handling as IP Speaker
Previously it had same volume handling as Amplifier
MTN-3582 Authorization required to send EMT changes to PSC
Earlier it was possible in some cases to send changes from EMT to PSC without authorization. This is now fixed.
MTN-3580 Channel shutdown is always reported as fault
Channel shutdown severity warning will not be affected by line fault severity settings, it will always be reported as fault.
MTN-2911 Zone selection - deselect after timeout issue fixed
Configuration with <Enable Timeout> for deselecting zone selection is now working
Known Issues
None