Anti-nuisance control (Event Handler)
From Zenitel Wiki
A master station should be able to disable calls from substations for a periode of time.
In the programming example below the master station dials 9535 + substation number to disable calls from that station for 15 minutes.
Directory number 9535 is a two-step event trigger, feature 95/0. When dialled, an event type 25 is triggered and the action string $SSC L%2.dir U2 moves the station to COS 2. COS 2 is by default empty, which will prevent calls to be initiated. Also a 15 minute timer is started, $ST L%2.dir W9000 L9999. The timer will trigger event type 21 when timing out. Command $SSC L%2.dir U1 will then move the station back to COS 1.
Set transfer to dummy number 345 when not in Call Requester Mode:
Event Owner: | The Master Station | ||
Event type: | 25 – Event trigger with parameter | ||
Subevent: | 0 | ||
When change to: | ON | ||
When related to: | All | ||
Action: | $SSC L%2.dir U2 | empty | $ST L%2.dir W9000 L9999 |
Reset transfer when in Call Requester Mode:
Event Owner: | Stations w/UDP Id: 8 (All stations) |
Event type: | 21 – Event timer |
When change to: | ON |
When related to: | Directory number: 9999 |
Action: | $SSC L%2.dir U1 |
Event 1:
Event Owner: The guard station Event type: 25 - Event trigger with parameter Subevent: 0 When change to: ON When Related To: All Action: $SSC L%2.dir U2 $ST L%2.dir W9000 L9999
Event 2:
Event Owner: Station w. UDP, Id: 8 (all stations) Event type: 21 - Event timeout Subevent: 0 When change to: ON When Related To: Directory number 0 | 9999 Action: