Actions

Tamper switch

From Zenitel Wiki

Revision as of 13:36, 1 December 2022 by Asle (talk | contribs) (Configuration)
AEIPS.png

The IP Vandal Resistant Substation with TKIE has the possibility to be fitted with a tamper switch. Making it possible to raise an alarm if the station is dismounted from the backbox.

Tamper Switch
(1008091010)

Configuration

In AlphaPro, create this event for the Tamper Switch:

Event handler configuration


Action commands:

$STM L101 L102 U100 'text 16'



The IP Substation must have I/O 3 defined as an input, which is the default setting.

Advanced AlphaCom -> I/O Settings


Mounting

Mounting instruction on Tamper Switch for IP Vandal Resistant Substation TKIE

Step 1: Remove the two nylon nuts shown below

Tamper1.png


Step 2: Attach the supplied spacers

Tamper2.png


Step 3: Mount the tamper switch board

Tamper3.png


Step 4: Move the button GND wire from the the TKIE board to the tamper switch board

Tamper4.png


Tamper5.png


Step 5: Use the supplied wires to connect GND and Input 3 as shown below

Tamper6.png