Actions

Bosch BIS - ICX-AlphaCom integration

From Zenitel Wiki

Revision as of 10:13, 15 August 2022 by Asle (talk | contribs) (Created page with "{{AI}} ==Introduction== Integration between the ICX system or AlphaCom system and the Bosch Building Integration System (BIS) is via OPC. ==Licensing== ===ICX=== ICX requir...")
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
AI.png

Introduction

Integration between the ICX system or AlphaCom system and the Bosch Building Integration System (BIS) is via OPC.

Licensing

ICX

ICX requires the presence of the appropriate API/OPC license.

  • 1002602306 - ILI-API64 - API License Supporting 64 Stations
  • 1002602309 - ILI-API512 - API License Supporting 512 Stations

With ICX it is possible to purchase a single Product Key which covers all stations connected to all ICX's in a network. ICX licenses can be stacked, i.e. 1x 1002602306 + 2x 1002602309 gives 1088 API licenses which can be used on 2 or more ICXs.

AlphaCom

The AlphaCom requires the presence of the appropriate API/OPC license. Note that every AlphaCom in an AlphaNet requires such a license.

  • 1009649901 - STENTOFON API License Supporting 40 Stations
  • 1009649902 - STENTOFON API License Supporting 80 Stations
  • 1009649903 - STENTOFON API License Supporting 160 Stations
  • 1009649904 - STENTOFON API License Supporting 240 Stations
  • 1009649905 - STENTOFON API License Supporting 320 Stations
  • 1009649906 - STENTOFON API License Supporting 400 Stations
  • 1009649907 - STENTOFON API License Supporting 552 Stations

Capabilities

The interface allows ICX or AlphaCom events to be transferred to BIS, and BIS to send commands to ICX/AlphaCom.

  • Call requests and established calls can be indicated on a map by changing the appearance of the remote intercom station icon
  • A call request can be answered from the screen by right clicking the icon and selecting 'Connect' from the drop down menu
  • In a similar way it is possible to cancel the established connection
  • Events in ICX/AlphaCom can be linked to actions in BIS --> A call request can cause a camera to stream video to a monitor

ICX/AlphaCom configuration

The OPC server communicates with ICX/AlphaCom TCP/IP port 61112 or 61113. In the Web interface, make certain that the TCP/IP port which will be used is enabled in the 'Filter-page' for the physical Ethernet port (ETH0 or ETH1) which is used to communicate with the OPC server.