Actions

Faulty Station Line (Event Type)

From Zenitel Wiki

Revision as of 22:05, 26 November 2007 by Asle (talk)

Event description

Event Owner: A station or an UDP group
Event type: 13 - Faulty station line
Subevent: N/A
When change to ON: A station's line monitoring has found a problem or if the whole ASLT board becomes faulty
When change to OFF: A station's line monitoring has found the station OK
When related to: N/A


Application

Switch over a PA-system to a standby circuit

Additional information

There is also a default "Faulty Line" event, which becomes active if one more stations are faulty. This event is used for general line error reporting. The reporting is configured from AlphaPro, Exchange & System -> RCI -> Faults: Faulty Line. Default setting is MST 1 0 28, which is by reporting line errors (28) to station 1.