Actions

Difference between revisions of "INCA Station Restore Factory Defaults"

From Zenitel Wiki

Line 4: Line 4:
 
* IP Video Door Stations - [[IP Video Door Station - 1401110100|1401110100]]/[[IP Video Door Station - 1401110200|1401110200]]
 
* IP Video Door Stations - [[IP Video Door Station - 1401110100|1401110100]]/[[IP Video Door Station - 1401110200|1401110200]]
  
This procedure is also applicable for the kits. Thi s requires that a push button is connected between pin 1 and pin 4 on connector P4.
+
This procedure is also applicable for the kits. This requires that a push button is connected between pin 1 and pin 4 on connector P4.
 
* [[IP Master Station Kit - 1008093000]]
 
* [[IP Master Station Kit - 1008093000]]
 
* The [[IP Substation Kit - 1008090200]]
 
* The [[IP Substation Kit - 1008090200]]

Revision as of 17:43, 17 March 2017

APS.png

This procedure is applicable for the stations:

This procedure is also applicable for the kits. This requires that a push button is connected between pin 1 and pin 4 on connector P4.


The unit can be set to use either Static IP or DHCP. Pay attention to the call LED during the restore procedure:

Connect a push button between pins 1 and 4
  1. Connect a push button (KEY1) between pin 1 and 4 on the P4 connector.
  2. While pressing the call button, power up the station and keep the button pressed.
  3. Release the button after exactly 2 flashes of the LED.
  4. Let the LED flash for exactly 2 more times (Static IP) or exactly 4 more times (DHCP), then press the button again.
  5. Keep the button pressed until the LED flashes fast 2 times (Static IP) or flashes fast 4 times (DHCP) indicating a successful reset.
  6. Release the button and the station will restart with the factory default settings.

Factory default values:

  • Station Mode: Pulse
  • Station IP address: 169.254.1.100 or DHCP
  • Username: admin
  • Password: alphaadmin

An IP Station may have to be reset to its original factory default settings if, for instance, the password to the webserver is forgotten.

The defaults can be either be set to Static IP or Activated DHCP (when there are many new IP Substations in an installation).

Restore to Factory Default for IP Stations without Display

This procedure is the recommended procedure for all IP Stations without Display:

The procedure can also be applied to:

The Factory Default procedure can be used to either set the station to use a Static IP address, or to use IP address from a DHCP server.

Restore with Static IP

Load Defaults without Display - 1.PNG
  1. While pressing the call button, power up the substation.
  2. When the substation LED starts blinking, release the call button after exactly 2 blinks.
  3. Let the LED blink for exactly 2 more times, then press the button again.
  4. Keep the button pressed until the LED blinks fast 2 times indicating a successful reset with static IP.
  5. Release the button and the substation will restart with the factory default settings.
Factory default values
Station Mode Pulse
Station IP address 169.254.1.100
AlphaCom IP address 169.254.1.5
Username* admin
Password* alphaadmin
* Software 01.06 and earlier: ADMIN/alphacom)

Restore with Activated DHCP

Load Defaults without Display - 2.PNG

The DHCP option is available from software version 01.07.

  • While pressing the call button, power up the substation.
  • When the substation LED starts blinking, release the call button after exactly 2 blinks.
  • Let the LED blink for exactly 4 more times, then press the button again.
  • Keep the button pressed until the LED blinks fast 4 times indicating a successful reset with activated DHCP.
  • Release the button and the substation will restart with the factory default settings.
Factory default values
Station Mode Pulse
Station IP address determined by DHCP server
AlphaCom IP address 169.254.1.5
Username* admin
Password* alphaadmin
* Software 01.06 and earlier: ADMIN/alphacom)