Actions

Difference between revisions of "IP-LCM Connections"

From Zenitel Wiki

(Indicators)
Line 19: Line 19:
  
  
For information on the [[TKIS Connections|TKIS-2 kit connections, see this link]]
+
See here for ior information on the [[TKIS Connections|TKIS-2 kit connections]]

Revision as of 10:23, 10 January 2019

IPLCM.png

Inputs

From the top left the inputs are numbered as pin 17 to pin 24. Each input has a corresponding input switch which toggles between closing contact and active input.

Outputs

From the left side the outputs are numbered as pin 17 to pin 24. Each output is a dual pole relay with normally open, normally close and common available on the pin header.
The bottom four outputs each has a corresponding switch. This allows forwarding power from the power forwarding connector to the relay normally open and common on each output.


Relay ratings:

  • Outputs: DPDT (NO, NC, COM)
  • Switched voltage: < 250VAC Rated (400VAC Max)
  • Switched Voltage: < 2000 VA max
  • Switching Current: < 8A rated (15A max, 4s)

Indicators

Each output has a LED which indicates if the output is active or not.


See here for ior information on the TKIS-2 kit connections