− | == TFIX V2 station with external speaker and signal device ==
| |
| | | |
− | In noisy areas an external speaker and/or a beacon lamp can be used to indicate an incoming call or PA announcement.
| |
− |
| |
− | == Single TFIX V2 with external speaker and beacon ==
| |
− | A single TFIX V2 with external speaker and beacon in the EX zone, where all the controlling equipment is located in the safe zone, either in the server room, or in a closed cabinet in a more convenient placement out in the field. <br/>
| |
− | The cabinet consist of:
| |
− | * 1 Flowire unit; FCDC3 (item 1008080310)
| |
− | * 1 48VDC Flowire PSU (item 2990000065)
| |
− | * 1 48VDC PSU for external speaker and beacon (item 2990000065)
| |
− | A junction box is needed out in the field to split the 48VDC between the TFIX V2 second power input and the beacon.
| |
− | * 1 Junction Box (item 2340110016)
| |
− |
| |
− | [[File:TFIXV2 Speaker Beacon Single.png|thumb|left|500px]]
| |
− | <br style="clear:both;" />
| |
− |
| |
− | [[File:Beacon and TA-10.png|thumb|left|500px|Detailed connection diagram]]
| |
− | <br style="clear:both;" />
| |
− |
| |
− | == Multiple TFIX'es with external signal device ==
| |
− | Multiple TFIX'es with external signal device in the EX zone, where all the controlling equipment is located in the safe zone in closed cabinets in a more convenient placements out in the field. <br/>
| |
− | Each cabinet consist of:
| |
− | * 1 Turbine extended kit; TKIE
| |
− | * 1 Turbine Relay board; TA-10
| |
− | * 1 24VDC or 230VAC PSU for external signal device
| |
− | * 1 Flowire unit; FCDC2
| |
− | * 1 24VDC Flowire PSU
| |
− |
| |
− | [[File:TFIX Beacon Multiple2.png|thumb|left|500px]]
| |
− | <br style="clear:both;" />
| |
− |
| |
− | ----
| |
− |
| |
− | Multiple TFIX'es with external signal device in the EX zone, where all controlling equipment is located in the server room. <br/>
| |
− | For every sixth TFIX with beacon you need:
| |
− | * 1 Turbine compact Kit; [[TKIS-2]]
| |
− | * 1 Multi-relay board; [[MRBD]]
| |
− | * 1 24VDC PSU: for the MRBD
| |
− | * 1 Flowire unit; FCDC2
| |
− | * 1 24VDC Flowire PSU
| |
− | * 6 Relay boxes; [[IRR-3 Relay unit|IRR-3]]
| |
− | * 6 External signal devices; Beacon BEX24O/BEX230O, or Signal bell/horn DHW2-24/DHH1-230
| |
− | * 6 24VDC or 230VAC PSU for external signal device
| |
− |
| |
− | [[File:TFIX Beacon Multiple1.png|thumb|left|500px]]
| |
− | <br style="clear:both;" />
| |
− | [[File:Beacon and IRR-3.png|thumb|left|500px|Detailed connection diagram]]
| |
− | <br style="clear:both;" />
| |
− |
| |
− | == Related articles ==
| |
− | * [[Turbine Compact and MRBD]]
| |
− | * [[IRR-3 Relay unit]]
| |