Difference between revisions of "AlphaCom system log"
From Zenitel Wiki
(→Device error) |
(→Board error) |
||
Line 38: | Line 38: | ||
=== Board error === | === Board error === | ||
− | + | '''Board Down''' is reported when the AMC-board fail to communicate with a board inside the module. Board error is reported down only (not up). Here the board in position 9 is reported down: | |
Oct 11 16:15:15 src@Johnson AlphaLog: N001.D065:.Exch:@D65.B09 Board Down | Oct 11 16:15:15 src@Johnson AlphaLog: N001.D065:.Exch:@D65.B09 Board Down | ||
Revision as of 15:39, 12 October 2007
The AlphaCom system log provides technical events for monitoring the health of the AlphaCom system. The system log includes the following type of events:
- Station Line error
- Board down
- Device/card cage error
- AGA line error
- Software error
- Remote input on/off
- Customized event logging
In AlphaPro (Exchange & System > System > Logs and Errors) it is possible to configure what events to include in the system log. By default all events are included.
It is also possible to configure customized events in the system log. This is done in the event handler by using the LOG command.
Contents
Description of log string
Common part Log event ----------------------------------------------------- ------------------------------------------ Oct 11 14:06:21 src@Johnson AlphaLog: N001.D065:.Exch:@D65.B01-2 Line Down: CD Open St 2 "102 -" --------------- ----------- -------- ---- ----- ---- ------------------------------------------ | | | | | | | | | | | | | +- Log event | | | | | +-------- Mandatory text | | | | +-------------- Source: Module number (65 is master module, 66-68 are slave modules) | | | +------------------- Source: Node number (Here: node 1) | | +-------------------------- Mandatory text | +--------------------------------------- Source: Exchange name +----------------------------------------------------- Date and time of log event
Log events
Station line error
The line monitoring feature of the AlphaCom will detect when there is a station line error. Stations are reported down only (not UP). Here line eroor is reported on station 102, board positon 1, line 2:
Oct 11 14:06:21 src@Johnson AlphaLog: N001.D065:.Exch:@D65.B01-2 Line Down: CD Open St 2 "102 -"
Board error
Board Down is reported when the AMC-board fail to communicate with a board inside the module. Board error is reported down only (not up). Here the board in position 9 is reported down:
Oct 11 16:15:15 src@Johnson AlphaLog: N001.D065:.Exch:@D65.B09 Board Down
Device error
Device Error is reported if the communication between the AlphaCom and the device fails. A "device" is normally a RIO unit). Here there is an error communicating with device #1:
Oct 10 17:51:36 src@Johnson AlphaLog: N001.D065:.Exch:@D01 Device Error
Device OK is reported when the communication becomes OK, and also after restart of the AlphaCom exchange:
Oct 10 17:51:37 src@Johnson AlphaLog: N001.D065:.Exch:@D01 Device OK
Device Missing is reported if the device is not responding after AlphaCom startup:
Oct 11 16:16:54 src@Johnson AlphaLog: N001.D065:.Exch:@D02 Device Missing
Card Cage
Reported OK when all boards in the module are up and running (the module is operational)
Oct 10 12:54:45 src@Johnson AlphaLog: N001.D065:.Exch:@D65 Card Cage OK
AGA error
An AGA error is reported if the audio link between two nodes in AlphaNet becomes faulty. Here the first line on board position 23 (B23-1) is reported faulty. The audio links are supervised by a test tones issued at regular intervals. Signal Level (SL) is the level measured when there is supposed to be a tone, Noise Level (NL) is the measured level when there is no tone (silence). Signal level is normally in the range 80 - 90. If the signal level is below 40, the AGA error is reported.
Oct 13 14:23:28 src@AlphaComE AlphaLog: N001.D065:.Exch:@D65.B23-1 AlphaNet Line Down:SL= 8 NL= 8
When the audio link becomes OK, the line is reported UP. Signal level 86 in this example:
Oct 13 14:23:59 src@AlphaComE AlphaLog: N001.D065:.Exch:@D65.B23-1 AlphaNet Line Up:SL=86 NL= 8
Remote Control Input RCI
RCI's are reported....
Oct 13 14:22:41 src@Johnson AlphaLog: N001.D065:.Exch:ALARM 1 ON. Oct 13 14:22:39 src@Johnson AlphaLog: N001.D065:.Exch:ALARM 1 OFF.
System reports
Oct 10 12:46:20 src@Johnson AlphaLog: N001.D065:.Exch:DP 33 CONN TCP-IP Server Port: 60001 IP:10.5.101.111 Oct 10 12:53:42 src@Johnson AlphaLog: N001.D065:.Exch:DP 33 DISC TCP-IP Server Port: 60001 IP: Oct 10 12:54:34 src@Johnson AlphaLog: N001.D065:.Exch:DP 39 CONN Uart /dev/tts/0 Oct 10 12:54:35 src@Johnson AlphaLog: N001.D065:.Exch:ALARM 8 ON. Oct 10 12:54:35 src@Johnson AlphaLog: N001.D065:.Exch:Temperature Alarm Oct 10 12:54:37 src@Johnson AlphaLog: N001.D065:.Exch:DP 04 CONN Uart /dev/tts/1 Oct 8 15:50:02 src@Johnson AlphaLog: N001.D065:.Exch:DP 03 CONN TCP-IP Client Port: 4001 IP: 10.5.101.42 Oct 8 15:49:48 src@Johnson AlphaLog: N001.D065:.Exch:DP 03 DISC TCP-IP Client Port: 4001 IP: