Distribution of Voice Alarm

A Remote Control Input (RCI) can be programmed so that an alarm voice message is automatically distributed to all stations or a group of when a contact closure is received (for example from a Fire Alarm Panel).

The feature includes volume and handset override for all InterGuard stations. This means that the evacuation message is distributed at maximum volume through all such stations. The evacuation message can be one of the default alarm messages or a customized message stored on the ASVP-board. It is also possible to use an external audio source for this purpose.

The activation of the alarm message can also be done manually from a station.

The possibility to set up such an alarm call must be restricted to certain stations only. This can be done in several ways:

Alarm Message Overview

Three alarm messages are available on the ASVP-board. The messages are typically used in evacuation situations where you want to distribute the alarm message to a group of stations.

Message no Message
8191 Fire alarm. Please stay calm and leave the building through the nearest exit. All exits are marked with green light. Don’t stop, but proceed completely out of the building. Wait for further information outside.
8192 The situation is now under control. The building can again be used. We are sorry for the inconvenience.
8193 An unexpected situation has occurred. Please stay calm and leave the building through the nearest exit. All exits are marked with green light. Don’t stop, but proceed completely out of the building. Wait for further information outside.



Customizing Voice Messages

With the Black AMC v.11 board there is no longer a need for the ASVP board. Using the inbuilt AlphaWeb it is possible to upload your own customized messages. The number of messages and the storage space is limitied by a license.

Requirements

The AMC-IP board must be version 5 or 6 (Black AMC-IP board)

The sound files must be in wav format:

  • 16 bit samplerate
  • 16 Khz
  • Mono

Uploading Voice Alarm Messages through AlphaWeb

The AlphaCom must have an Audio Messaging license.

Log on to AlphaWeb, System Configuration > Messaging:

thumb


Select Message Group, Group Index, and File to Upload.

Examples of Message Groups and Index:

Message Group 30, Group Index 1 - 9: Alarm messages 8191 – 8199
Message Group 10, Group Index 47: Call Request message ”Your call is registered, please wait”