Difference between revisions of "Door Opening using Dummy Number (Event Handler)"
From Zenitel Wiki
(→Solution) |
|||
Line 24: | Line 24: | ||
|} | |} | ||
<br><br> | <br><br> | ||
+ | |||
+ | Explanation: | ||
+ | * Subevent 6 means digit 6 | ||
+ | * When Change to ON meand when the digit is pressed (not released) | ||
+ | * RCO 6 ON 20 means pulse RCO 6 for 2,0 seconds | ||
+ | * $DISCON_ST L%1.dir U2: disconnect the station with successtone |
Revision as of 14:01, 26 October 2007
Situation
Some gates are not equipped with door stations, but the operator want to use the same Door Opening procedure to open the door. When the operator gets a signal that there is someone at the door he should dial a dummy number, then press digit 6 to operate a relay output (i.e. a RCO).
Solution
For this function the two-step event trigger, feature 105, can be used. In AlphaPro, Directory & Features, create a directory number, feature 105, for each door. Directory number 9545 is included by default. In Exchange & System -> Events, create a new event with the following parameters:
Event Owner: | The operator station or an UDP group |
Event type: | 25 – Event Trigger w/User Parameter |
Subevent: | 6 |
When change to:: | ON |
When related to: | Directory number: 9545 |
Action: | RCO 4 ON 20 |
$DISCON_ST L%1.dir U2 |
Explanation:
- Subevent 6 means digit 6
- When Change to ON meand when the digit is pressed (not released)
- RCO 6 ON 20 means pulse RCO 6 for 2,0 seconds
- $DISCON_ST L%1.dir U2: disconnect the station with successtone