− | For this function the two-step event trigger, feature 105, can be used. In AlphaPro, Directory & Features, create a directory number, feature 105, for each door. Directory number 9545 is included by default. In Exchange & System -> Events, create a new event with | + | For this function the two-step event trigger, feature 105, can be used. In AlphaPro, Directory & Features, create a directory number, feature 105, for each door. Directory number 9545 is included by default. In Exchange & System -> Events, create a new event. |
+ | |||
+ | Using the example below, any station can dial 9545 + 6 to trigger RCO 4 for 2 seconds, and disconnect with success-tone: | ||
[[Image:Event 25 Event trigger w Parameter.jpg|thumb|right|Event Handler configuration]] | [[Image:Event 25 Event trigger w Parameter.jpg|thumb|right|Event Handler configuration]] | ||
{| | {| |
Revision as of 14:04, 26 October 2007
Situation
Some gates are not equipped with door stations, but the operator want to use the same Door Opening procedure to open the door. When the operator gets a signal that there is someone at the door he should dial a dummy number, then press digit 6 to operate a relay output (i.e. a RCO).
Solution
For this function the two-step event trigger, feature 105, can be used. In AlphaPro, Directory & Features, create a directory number, feature 105, for each door. Directory number 9545 is included by default. In Exchange & System -> Events, create a new event.
Using the example below, any station can dial 9545 + 6 to trigger RCO 4 for 2 seconds, and disconnect with success-tone:
Event Owner: | The operator station or an UDP group |
Event type: | 25 – Event Trigger w/User Parameter |
Subevent: | 6 |
When change to:: | ON |
When related to: | Directory number: 9545 |
Action: | RCO 4 ON 20 |
$DISCON_ST L%1.dir U2 |
Explanation
- Subevent 6: digit 6
- When Change to ON: When the digit is pressed (not released)
- RCO 6 ON 20: Pulse RCO 6 for 2,0 seconds
- $DISCON_ST L%1.dir U2: Disconnect the station with successtone