PrisCom station - Configuration
From Zenitel Wiki
This article describes how to configure the Prison Stations model 1007061000 and 1007063000.
Contents
- 1 Software requirements
- 2 Decide the configuration starting point
- 3 Basic feature programming
- 4 Advanced feature programming
- 5 Description of the PrisCom database
- 5.1 DAK Keys on physical numbers 500 and 501
- 5.2 IND Commands used by Prison Stations
- 5.3 Display data commands
- 5.4 Volume Override
- 5.5 Changing the privacy setting
- 5.6 Changing Offline mode operation
- 5.7 Changing Guard Presence timeout-alarm
- 5.8 Changing Sensor Key sensitivity
- 5.9 Pulse relay instead of static relay for Relay Control output
- 5.10 Scream Alarm
- 5.11 Event Handler programming
- 5.11.1 The use of UDD variables
- 5.11.2 External light control ON
- 5.11.3 External light control OFF
- 5.11.4 Conversation start
- 5.11.5 Conversation end
- 5.11.6 Private Ringing start
- 5.11.7 Private Ringing end
- 5.11.8 Initialization of stations. DAK redirection
- 5.11.9 LOG when a station is faulty
- 5.11.10 Call Request - Event Trigger 9550
- 5.11.11 Alarm Call Request - Event Trigger 9551
- 5.11.12 Tamper Alarm - Event Trigger 9552
- 5.11.13 Guard Present 1 - Event Trigger 9553
- 5.11.14 Guard Present 2 - Event Trigger 9554
- 5.11.15 Guard Present timeout
- 5.11.16 Guard reset - Event Trigger 9555
- 5.11.17 Power Fail ON - Event Trigger 9556
- 5.11.18 Power Fail OFF - Event Trigger 9557
- 5.11.19 Light switch - Event Trigger 9558
- 5.11.20 Scream Alarm (VOX) - Event Trigger 9561
- 5.11.21 Silent call
- 5.11.22 LOG Conversation start
- 5.11.23 LOG Conversation end
- 5.11.24 LOG Private Ringing start
- 5.11.25 Report faulty stations to AlphaVision
- 6 Adding Guard Station in different node
- 7 Offline mode
Software requirements
- AMC software v.9.09 or later
- AlphaPro 9.21 or later
"Scream alarm from idle" is available from station software 01.02.
Decide the configuration starting point
When configuring a system with the 1007061000/1007063000 stations there are two options:
- Start with a new AlphaPro database and fill in the parameters from scratch (Basic features)
- Use a preprogrammed PrisCom database from Zenitel (Advanced features)
"Basic features" are:
- Call Button
- Program Step button (without displaying selected channel)
"Advanced features" means support for:
- Light button
- External key switch
- Corridor lamp and/or group lamp
- Display for selected program channel
- Tamper alarm and Power failure alarm
- Scream alarm
- AlphaVision
When using the advanced features of the station, it is highly recommended to use the preconfigured AlphaPro database as a starting point. The advanced features is depending a lot on Event Handler programming, and much work is saved by using an already preconfigured database.
Basic feature programming
The 7061 and 7063 uses “Two tone DAK signaling", not regular DAK signaling
- In Users & Stations -> User Preferences set DAK signaling to "(3) Two tone signaling w/ack“
- In Users & Stations -> DAK assign numbers to the panel buttons:
- DAK 2 = Call button, normally configured to "I 623 I xxx", where xxx is the number of the Guard Station
- DAK 3 = Program Step button, normally configured to "I 790" (button not available on the 100 7061 000)
Advanced feature programming
Download the PrisCom database from the download site. Copy the PrisCom database to the AlphaPro Database folder (E.g. C:\Program files\AlphaPro\Database).
Start AlphaPro and select the PrisCom database. Verify that the PrisCom database is visible.
Guard station configuration
- In Users & Stations window, highlight the guard station in the list box, select the tab UDP, and include the guard station in UDP 1
- In Groups -> Local Groups, select group 10 (or another free group) and include the guard station in this “Guard group”. This is required even with a single guard station.
- Continue with step 1 and 2 for all guard stations.
Prison station configuration
- In Users & Stations window, highlight the prison station in the list box, select the tab UDP, and include the prison station in UDP 2
- In Users & Stations window, highlight the prison station in the list box, select the tab UDP, and enter the “Guard group” index number (e.g. 10) in the Used Defined Parameter field. This is the target for calls from this station. When the call button is presses on the prison station, a call request is sent to all stations in this group.
- Continue with step 1 and 2 for all prison stations.
Notes on DAK programming:
- No DAK programming is required
- The event handler programming in the PrisCom database will automatically set “Two tone DAK signaling”, and redirect the DAK keys to point to physical station 500 and 501
- Physical station 500 and 501 have preconfigured DAK keys according to the PrisCom Station features.
Note that only Prison Stations model 1007061000 or 1007063000 should be in UDP 2. If there are other types of prison stations in the system, they should not be in UDP 2.
Upload configuration to the AlphaCom
- After the PrisCom stations are connected to the AlphaCom, upload the configuration to the AlphaCom by selecting “SendAll” from AlphaPro
- When the upload is finished, reset the AlphaCom. When the exchange is up and running, reset once more
- Now do a “GetAll” to update AlphaPro with the correct settings
Note that every time a new Prison Station is added to the system, the above procedure should be used (SendAll, 2 x reset, GetAll).
The dual reset procedure is only required after adding new PrisCom stations to the system. The first reset will trigger the "Faulty Line OFF" event. This event will automatically program the DAK keys and enable the "Two Tone DAK signalling", and it will send configuration data to the Prison Stations. The second reset is to make the changes take effect. At this stage the AlphaCom configuration is different from the AlphaPro. The GetAll is required for AlphaPro to reflect the actual configuration in the exchange.
Description of the PrisCom database
The Prison Stations 7061 and 7063 are mainly operating by sending a "Two tone" DAK digits to the exchange for input events, and receiving display data messages in response. The Prison Stations are the only station types which are using the "double-tone" DAK signalling. The event handler programming in the PrisCom database will automatically set the Prison stations to use “Two tone DAK signaling”.
Display messages are used to e.g. turn lamps on, set alarm preparation mode during guard presence, or control other features. These messages are mostly defined as commands in the AlphaCom event handler. To change functionality one will have to change these commands or add/remove/change events.
DAK Keys on physical numbers 500 and 501
The Priscom stations have common DAK key programming. The DAK configuration is programmed on physical number 500 and 501, and the event handler programming in the PrisCom database will upon reset cause the AlphaCom to automatically program the DAK’s of the Prison Stations to point to these physical numbers 500 and 501. The DAK table of the physical numbers 500 and 501 are preconfigured according to the table below. Most of the numbers are Event Triggers, starting from 9550 and upwards. Actions for these custom event triggers are defined in the event handler, using the event “15 Event Trigger Feature”.
DAK keys 1-10 is from physical number 500, and DAK key 11-20 is from physical number 501.
DAK key | DAK string | Description |
1 | E 9558 | Panelkey 1: Light button |
2 | M I 9550 | Panelkey 2: Call Request / "Answer" on incoming calls |
3 | I 790 | Panelkey 3: Program button |
4 | E 9551 | Panelkeys in alarm mode: Alarm call |
5 | E 9552 | Tamper switch |
6 | E 9553 | IN KEY1 (Guard Keyswitch 1) |
7 | E 9554 | IN KEY2 (Guard Keyswitch 2) |
8 | E 9555 | Guard Keyswitch Reset |
9 | E 9556 | Power fail (Voltage must be down in 7-8Vdc for 100ms before hardware notice to low voltage) |
10 | E 9557 | Power OK |
11 | IN1 ON (Input 1): (Set as default alarm input during guard presence by display command 0x63. See below) | |
12 | M I 9550 | IN1 OFF (Input 1): External Call Request / "Answer" on incoming calls |
13 | IN2 ON (Input 2) | |
14 | IN2 OFF (Input 2) | |
15 | IN3 ON (Input 3) | |
16 | IN3 OFF (Input 3) | |
17 | IN4 ON (Input 4) | |
18 | IN4 OFF (Input 4) | |
19 | E 9561 | Scream detector |
20 |
IND Commands used by Prison Stations
The outputs on the Prison Stations are controlled by IND commands executed in the event handler. There are eight outputs:
IND output | Description | Comment |
1 | L1 - Output 1 | Red lamp (Call) |
2 | L2 - Output 2 | Green lamp (Present) |
3 | L3 - Output 3 | Blue lamp (Tamper alarm) |
4 | L4 - Output 4 | Group lamp |
5 | L5 - Output 5 | Spare |
6 | L6 - Output 6 | Spare |
7 | Relay | Cell light |
8 | Call LED, External LED | Also controlled by microphone active (polarity reversal of C/D-wire during conversation) |
Syntax:
- IND <station phys.no> <output> <1> <Indtype> [state]
Example:
- IND %1.phy 1 1 3 ON: Turn the red lamp ON, flashing
Display data commands
Some properties of the Prison Station are configured in the station it self. The configuration data is sent to the Prison Station as display data, using the Event Handler and the $DSPL command.
The format is as follows:
$DSPL <station> <length>
- Station: The prison station
- Length: The length of the data string.
- Data: Display data command and parameters. For the Prison Station programming, sequential hex values are used to make the string.
Cmd | Parameters | Default | Description |
0x23 | None | Volume override ON. | |
0x24 | None | Volume override OFF. | |
0x45 | None | Disable call LED. ("Silent monitoring" mode). | |
0x46 | None | Enable call LED. (End "Silent monitoring" mode). | |
0x47 | None | Set flag for preventing call-request button from generating a callrequest in station's offline mode | |
0x48 | None | Clear flag for preventing call-request button from generating a callrequest in station's offline mode | |
0x60 | 00 = off, 01 = on | 60 00 | Set "alarm preparation mode" on/off. When ON, all panel buttons trigger DAK 4. |
0x61 | 00 = static relay, >00 = pulse length | 61 00 | Select light relay type: Static or pulserelay. |
0x62 | 00 = none, 01 = type1 | 62 01 | Select offline mode operation type. Required for offline mode operation. |
0x63 | 63 02 00 00 00 | Configure general inputs. One byte for each input. Select inverted input (bit0) and alarm-trigger input (bit1) | |
0x64 | 64 A0 08 00 23 | Configure Scream alarm detector. Volume level (00=set default), min scream-time (00=set default), max scream-time, min pause before re-enabling alarm. Times in 100ms resolution. (Note: Parameters are not saved to EEPROM, and lost when the station is moved). | |
0x65 | 65 0960 | Set guard alarm timeout. Value is 16-bit, 100ms resolution. Max value = 0x199A (11 minutes). | |
0x66 | 66 00 | Select front-panel key types: Capacitive sensor-key (0) or switch input (1). Each bit represents one key (bit0 = light-button, bit1 = callrequest, bit2 = program, bit3 = vol up, bit4 = vol dn). | |
0x67 | 67 00 0A | Configure keyswitch inputs: Static switches (00) or toggle-switches (01). Delay after activation in 100ms resolution. | |
0x68 | 68 06 | Set default volume override level (selected by messages 0x23/0x24). Min=00 Max=06. | |
0x70 | None | 70 | Restore EEPROM defaults. |
Examples:
$DSPL L%1.dir U2 6100 '' : Set light relay to static mode
$DSPL L%1.dir U1 23 '' : Volume override ON
Note:
The parameters are followed by two single apostrophes ('). Closing single quotation marks (‘…’) are not valid. A text editor like Word (and others) tends to convert apostrophes to single quotation marks, which will not work.
Volume Override
When using the PrisCom database and a conversation is established, the volume set by the user is overridden, and a preset volume is used. The preset volume is defined by the display data command 0x68. By default set to maximum ($DSPL L%1.dir U2 6806'').
The volume override ON is set by the display data command 0x23 when the conversation starts ($DSPL L%1.dir U1 23''), and the volume override OFF is set by the command 0x24 when the conversation ends ($DSPL L%1.dir U1 24'' ).
If the preset override volume is too loud, the following event can be modified:
Owner: Event: Change to: UDP 2 13-Faulty station line OFF
In the "Action field" find the line:
- $DSPL L%1.dir U2 6806'', and change 06 to a value 00-05. The value 00-06 sets what volume level to use when volume override is activated.
If volume override is not wanted at all, one can delete the line $DSPL L%1.dir U1 23'' from the "Conversation Incoming ON" event.
Changing the privacy setting
By default the Prison Stations are set in privacy mode. This means that a guard can’t call directly into the cell, but the prisoner has to accept the call by pressing the call button.
To change the station to operate in Open mode, the following event must be modified:
Owner: Event: Change to: UDP 2 13-Faulty station line OFF
In the "Action field" find the line:
- $SNV Q55 W5 W8 W%1.phy W17 (Prison stations in Private mode)
Change into:
- $SNV Q39 W5 W8 W%1.phy W17 (Prison stations not in Private mode)
Changing Offline mode operation
The cell station operates in both "online" mode when connected to AlphaCom and "offline" mode when connection is lost and only 24V power is used. In this mode the external lamps are used for status signalling. This operation is mostly hardcoded in the station. In case the station is used in an installation where offline mode operation should be turned off or changed, the following event can be modified:
Owner: Event: Change to: UDP 2 13 Faulty station line OFF
In the "Action field" find the line:
- $DSPL L%1.dir U2 6201 '' (Offline operation mode type 01)
Change into:
- $DSPL L%1.dir U2 6200 '' (Offline operation turned off)
Note: In current station software v1.02 there is only one available offline operation mode: 01. Other modes may be added in the future.
Changing Guard Presence timeout-alarm
When a guard marks his presence in a cell by turning the keyswitch to position 2, an alarm timeout is activated (no timeout for keyswitch position 1). The value of this timeout can be adjusted in the event handler.
The following event must be modified:
Owner: Event: Change to: Related to: UDP 2 15-Event trigger ON 9554
Modify this action command:
- $ST L%1.dir W2400 L9554
The value “W2400” is in 100ms resolution, which gives a 240 seconds (4 minutes) timeout. Change to desired value. Value is in decimal format.
Changing Sensor Key sensitivity
By default the sensor buttons are set for high sensitivity, making it possible to operate the station with sanitary or latex gloves.
If the station is located in an area with high humidity, for instance just outside a shower area, there is a risk that the station could generate ghost calls. It is possible to change the sensor buttons to a lower sensitivity. The side effect is that gloves cannot be used to trigger calls.
The following event must be modified:
Owner: Event: Change to: UDP 2 13-Faulty station line OFF
Modify this action command:
- $DSPL L%1.dir U2 6600 '' (High key sensitivity)
into:
- $DSPL L%1.dir U2 661f '' (Low key sensitivity)
Pulse relay instead of static relay for Relay Control output
By default the Relay Control output (connector P1/5 and P1/6) is configured as a static relay changing on/off each time the “light” button on the prison station is pressed. This can be changed to a pulse relay operation if such a relay is used.
The following event must be modified:
Owner: Event: Change to: UDP 2 13-Faulty station line OFF
Modify this action command:
- $DSPL L%1.dir U3 6100 '' (Static relay)
into:
- $DSPL L%1.dir U3 610A '' (Pulserelay, 10*10ms pulsetime)
The parameter "0A" to the display data command 0x61 in the string above defines the pulsetime in 10ms resolution. Value is in hex format.
If pulse relay is used, the state of the light (on or off) is unknown and some events should be modified accordingly. Some action lines should be deleted. They are highlighted by green color in the following event handler description.
Scream Alarm
The display data command 0x64 is used to set the level and duration necessary to trigger the scream alarm.
0x64 <volume level> <min-time> <max-time> <pause> [mode]
Default command is 64 A0 08 00 23, the values are in hexadecimal.
- Volume level is the trigger level 00-FF, A0 is default. See table below.
- Minimum scream time = 08 Default (800ms). Noise must be present this long to trigger an alarm
- Maximum time = 00 default (optional). Noise longer than this do not trigger an alarm. Can be used to surpress alarms caused by sudden background noise which is present for a long time (longer than specified in this parameter).
- Pause is minimum time for re-enabling alarm is default 23 (= 3500ms)
- Mode is an optional parameter, available from station software 01.02. 00=Scream alarm only in "alarm preparation mode". 01=Scream alarm from idle.
The scream alarm is triggering DAK 19, and for testing the DAK key can be programmed to “I 101” or similar.
The default behavior of the Prison Station is that the scream alarm is active only when the station is in "alarm preparation mode" (controlled by display data command 0x60), i.e. when the guard is present by turning the key switch in position 1 or 2.
For special applications it is possible to enable scream alarm also from idle:
- $DSPL L%1.dir U6 64A008002301 '' : Enable scream alarm from idle
- $DSPL L%1.dir U6 64A008002300 '' : Enable scream alarm only when in "alarm preparation mode" (Default)
Relation between sound pressure and the programmed scream alarm volume:
Volume (00-FF) |
Sound Pressure (dBA, +/-3dB) |
40 | 74 |
50 | 77 |
60 | 80 |
78 | 83 |
90 | 86 |
A8 | 89 |
C0 | 92 |
D0 | 95 |
E0 | 98 |
F0 | 101 |
Example: $DSPL L%1.dir U5 6478080023 '' will set the scream alarm level to 78 (83 dBA).
Event Handler programming
This paragraph describes the event handler programming used in the PrisCom database.
The use of UDD variables
User Defined Data (UDD) are variables which can be used to store status information. In the PrisCom database the physical number of the station is used as index for the UDD. If there is a need to use additional UDD's in the database, one must avoid using index numbers in the same range as the physical numbers for the Prison Stations. In order to store several statuses in one UDD a bitmask is used - one word per station:
Bit (value) | Description |
11 (2048) | (Not used) |
10 (1024) | Call request mode / tamper call |
9 (512) | Guard present |
8 (256) | Light status on |
7-0 | (Not used) |
Examples of using UDD's:
- Read: %udd(%1.phy) will return the content of the UDD
- Write: WUDD %1.phy 3 will write the value 3 in the UDD
External light control ON
Guard dials "9559 + 103 + C" to turn the cell-light relay on. Dirno 9559 is feature no 95/0.
Event Owner: UDP 1 (Guards) Event Type: 25 - Event Trigger w/Parameter Sub Event: 0 When Change To: ON Related To: All Action: IND %2.phy 7 1 1 ON
External light control OFF
Guard dials "9560 + 103 + C" to turn the cell-light relay off. Dirno 9560 is feature no 95/1.
Event Owner: UDP 1 (Guards) Event Type: 25 - Event Trigger w/Parameter Sub Event: 1 When Change To: ON Related To: All Action: IND %2.phy 7 1 1 OFF
Conversation start
When conversation is established, "volume override" is activated and status lamps are switched off.
Event Owner: UDP 2 (Prison stations) Event Type: 07 - Conversation incoming When Change To: ON Related To: All Action: $DSPL L%1.dir U1 23 '' Volume override ON IF %op(%op(%udd(%1.phy),&,1024),==,1024) If the station is in call request mode or tamper call (bit 10) WUDD %1.phy,%op(%udd(%1.phy),&,64511) Reset Call Request mode / tamper call (bit 10) IND %1.phy 3 1 1 OFF Turn tamper-lamp off when communication is established IND %1.phy 1 1 1 OFF Turn call-lamp off when communication is established IND %1.phy 4 1 1 OFF Turn group-lamp off when communication is established ENDIF
Conversation end
When the conversation is ended, "volume override" is turned off.
Event Owner: UDP 2 (Prison stations) Event Type: 07 - Conversation incoming When Change To: OFF Related To: All Action: $DSPL L%1.dir U1 24 '' Volume override OFF
Private Ringing start
When the Prison station starts to ring, and the station already has made a Call Request or the Guard is already present (Key Switch in pos.1 or 2), then autoanswer is triggered (simulating M-key press), and the converation is automatically established. If no autoanswer (still ringing), a flag is set to prevent the call button from triggering the call lamps when the button is pressed to answer the call.
Event Owner: UDP 2 (Prison stations) Event Type: 09 - Private Ringing mode When Change To: ON Related To: All Action: IF %op(%op(%op(%udd(%1.phy),&,512),==,512),||,%op(%op(%udd(%1.phy),&,1024),==,1024)) If Guard Present (bit 9) or Call Req mode (bit 10) $M L%1.dir Simulate M-key push to connect the call without ringing $MREL L%1.dir STOP ENDIF $DSPL L%1.dir U1 47 '' Set flag for preventing call-request button from generating a callrequest in station's offline mode
Private Ringing end
When the ringing stops, clear the flag that prevents the call button from triggering the call lamps when the button is pressed to answer the call.
Event Owner: UDP 2 (Prison stations) Event Type: 09 - Private Ringing mode When Change To: OFF Related To: All Action: $DSPL L%1.dir U1 48 '' Clear the flag that prevents the call button from generating a callrequest in station's offline mode
Initialization of stations. DAK redirection
When the prison station is reported up (e.g. after a system restart), this event will send configuration data to the station using the $DSPL command. The event will also, with an IF statement, check if the station is already configured as a Prison station in the AMC by checking the station flags2 bits for Two-tone signaling and audio program display. If not already configured with these settings, they will be applied, and the DAK key 1 will be programmed to ">501" and DAK 2 to ">502".
Event Owner: UDP 2 (Prison stations) Event Type: 13 - Faulty Station line When Change To: OFF Related To: All Action: LOG "St %1.phy, %1.dir %1.nam: Line fault reset" Send to System log that station is OK $DSPL L%1.dir U2 6100 '' Set light relay type to static $DSPL L%1.dir U2 6201 '' Offline mode: 01 $DSPL L%1.dir U5 6302000000 '' Set input 1 (external call button) to alarm trigger input when station is in alarm mode. $DSPL L%1.dir U5 64A0080023 '' Configure scream alarm. Volume = A0, min. scream time = 08 (800ms), max. time = 00, pause = 23 (3500 ms) $DSPL L%1.dir U3 650960 '' Guard timeout: 0x0960 = 2400 ms = 4 min. $DSPL L%1.dir U2 6600 '' Key type: Capacitive sensor keys $DSPL L%1.dir U3 67000A '' Keyswitch: Static $DSPL L%1.dir U2 6806 '' Max. Volume override level = 06 IF %OP(%op(%GNV(5,8,%1.phy,17),&,65519),==,39) Is testing the bit pattern 1X0111 against st_profile[n].flags2 (but removes bit 5 first, counted from 1, this bit controls privacy.) STOP Stop if the bit pattern already is 1X0111, as the station is already set as Prison Station. ENDIF $SNV Q55 W5 W8 W%1.phy W17 Q55: Sets the bit pattern to 110111 (display, two-tone w/ack, privacy). Q39: Sets the bit pattern to 100111 (display, two-tone w/ack) $SNV Q16496 W5 W8 W%1.phy W16 Sets bit 4, 5, 6 and 14 in station_flags1. $SNV Q62 W5 W8 W%1.phy W0 W0 W0 Configure DAK 1 to ">500" and DAK 2 to ">501". Set first char in DAK 1 to ">" $SNV Q53 W5 W8 W%1.phy W0 W0 W1 Set second char in DAK 1 to "5" $SNV Q48 W5 W8 W%1.phy W0 W0 W2 Set third char in DAK 1 to "0" $SNV Q48 W5 W8 W%1.phy W0 W0 W3 Set fourth char in DAK 1 to "0" $SNV Q62 W5 W8 W%1.phy W0 W1 W0 Set first char in DAK 2 to ">" $SNV Q53 W5 W8 W%1.phy W0 W1 W1 Set second char in DAK 2 to "5" $SNV Q48 W5 W8 W%1.phy W0 W1 W2 Set third char in DAK 2 to "0" $SNV Q49 W5 W8 W%1.phy W0 W1 W3 Set fourth char in DAK 2 to "1"
LOG when a station is faulty
This event is triggered when a station is reported faulty, and an error message is sent to the System log.
Event Owner: UDP 2 (Prison stations) Event Type: 13 - Faulty Station line When Change To: ON Related To: All Action: LOG "St %1.phy, %1.dir %1.nam: Line fault" Send to System log that station is FAULTY
Call Request - Event Trigger 9550
This event is triggered when the call button is pressed. A Call Request is sent to the Guard station(s), and the call- and group lamps are turned ON.
Event Owner: UDP 2 (Prison stations) Event Type: 15 - Event Trigger Feature Sub Event: 0 When Change To: ON Related To: 9550 Action: $SM L%1.dir NG%1.exp U103 NM18 GV U3 'Call' Send call request to the "Guard Group" (%1.exp) with priority 103 LOG "St %1.phy, %1.dir %1.nam: Cell callrequest" Send information to System log WUDD %1.phy,%op(%udd(%1.phy),|,1024) Set Call Request mode / tamper call (bit 10) IND %1.phy 1 1 1 ON Turn call-lamp on IND %1.phy 4 1 1 ON Turn group-lamp on
Alarm Call Request - Event Trigger 9551
This event is triggered when the status is "Guard Present" (i.e. the keyswitch is in position 1 or 2), and any button is pressed. An Alarm Call Request is sent to the Guard station(s), the lamps are turned ON, and a message is sent to AlphaVision.
Event Owner: UDP 2 (Prison stations) Event Type: 15 - Event Trigger Feature Sub Event: 0 When Change To: ON Related To: 9551 Action: $STM L%1.dir NG%1.exp U143 '%1.dir Alarm!' U1 Send alarm request to the "Guard Group" (%1.exp) with priority 143 LOG "St %1.phy, %1.dir %1.nam: Alarm call!" Send information to System log IND %1.phy 1 1 3 ON Turn call-lamp on, flashing IND %1.phy 4 1 3 ON Turn group-lamp on, flashing IND %1.phy 2 1 1 ON Turn guard present-lamp on @01FF M7C01 U01 W%1.phy U%3.CHG(3,0) Send status message to AlphaVision
Tamper Alarm - Event Trigger 9552
This event is triggered when the tamper alarm switch is activated. A message is sent to the Guard station(s), the tamper lamp is turned ON, and a message is sent to AlphaVision.
Event Owner: UDP 2 (Prison stations) Event Type: 15 - Event Trigger Feature Sub Event: 0 When Change To: ON Related To: 9552 Action: $SM L%1.dir NG%1.exp U36 NM18 GV U2 'Tamper alarm!' Send tamper alarm message to the "Guard Group" (%1.exp) with priority 36 LOG "St %1.phy, %1.dir %1.nam: Tamper Alarm!" Send information to System log WUDD %1.phy,%op(%udd(%1.phy),|,1024) Set Call Request mode / tamper call (bit 10) IND %1.phy 3 1 1 ON Turn tamper-lamp on @01FF M7C01 U01 W%1.phy U%3.CHG(2,0) Send status message to AlphaVision
Guard Present 1 - Event Trigger 9553
This event is triggered when the Guard Keyswitch is turned in position 1. Audio program is switched off, a "Guard Present" message is sent to the Guard station(s), the station is set in alarm mode (i.e. all buttons works as alarm buttons), the lamp status is updated, and a message is sent to AlphaVision.
Event Owner: UDP 2 (Prison stations)
Event Type: 15 - Event Trigger Feature
Sub Event: 0
When Change To: ON
Related To: 9553
Action:
$TPROG L%1.dir U0 Switch off audio prog temporarily
$CANM L%1.dir NG%1.exp Cancel all requests from this station
$STM L%1.dir NG%1.exp U33 '%1.dir Grd present' U0 Send "Guard present" message
LOG "St %1.phy, %1.dir %1.nam: Guard present" Send information to System log
$DSPL L%1.dir U2 6001 '' Cmd 60 01: Set Alarm preparation mode
WUDD %1.phy,%op(%udd(%1.phy),|,512) Set Guard present (bit 9)
IND %1.phy 1 1 1 OFF Turn call-lamp off
IND %1.phy 4 1 1 OFF Turn group-lamp off
IND %1.phy 2 1 1 ON Turn guard present-lamp on
IND %1.phy 7 1 1 ON Switch on the cell light
@01FF M7C01 U01 W%1.phy U%3.CHG(3,0) Send status message to AlphaVision
If pulse relay is used, the state of the light (on or off) is unknown and the lines in green should be removed.
Guard Present 2 - Event Trigger 9554
This event is triggered when the Guard Keyswitch is turned in position 2. Audio program is switched off, a "Guard Present" message is sent to the Guard station(s), the station is set in alarm mode (i.e. all buttons works as alarm buttons), a 4 minute alarm timer is started, the lamp status is updated, and a message is sent to AlphaVision.
Event Owner: UDP 2 (Prison stations)
Event Type: 15 - Event Trigger Feature
Sub Event: 0
When Change To: ON
Related To: 9554
Action:
$TPROG L%1.dir U0 Switch off audio prog temporarily
$CANM L%1.dir NG%1.exp Cancel all requests from this station
$STM L%1.dir NG%1.exp U33 '%1.dir Grd present' U0 Send "Guard present" message
LOG "St %1.phy, %1.dir %1.nam: Guard present" Send information to System log
$DSPL L%1.dir U2 6001 '' Cmd 60 01: Set Alarm preparation mode
WUDD %1.phy,%op(%udd(%1.phy),|,512) Set Guard present (bit 9)
$ST L%1.dir W2400 L9554 Start a 240 second alarm-timer
IND %1.phy 1 1 1 OFF Turn call-lamp off
IND %1.phy 4 1 1 OFF Turn group-lamp off
IND %1.phy 2 1 1 ON Turn guard present-lamp on
IND %1.phy 7 1 1 ON Switch on the cell light
@01FF M7C01 U01 W%1.phy U%3.CHG(3,0) Send status message to AlphaVision
If pulse relay is used, the state of the light (on or off) is unknown and the lines in green should be removed.
Guard Present timeout
This event is triggered when the timer that was started by turning the Guard Keyswitch in position 2, expires. An Alarm Call Request is sent to the Guard station(s) and the lamps are turned ON.
Event Owner: UDP 2 (Prison stations) Event Type: 21 - Event Timeout When Change To: ON Related To: 9554 Action: $STM L%1.dir NG%1.exp U143 '%1.dir Alarm!' U1 Send "Alarm" message to Guard Group LOG "St %1.phy, %1.dir %1.nam: Alarm call! (timeout)" Send information to System log IND %1.phy 1 1 3 ON Turn call-lamp on, flashing IND %1.phy 4 1 3 ON Turn group-lamp on, flashing IND %1.phy 2 1 1 ON Turn guard present-lamp on
Guard reset - Event Trigger 9555
This event is triggered when the Guard Keyswitch is turned back to idle position 0. Audio program is switched back on, all messages from this station is cleared, alarm mode and lamps are cleared, alarm timer is stopped, and a message is sent to AlphaVision.
Event Owner: UDP 2 (Prison stations)
Event Type: 15 - Event Trigger Feature
Sub Event: 0
When Change To: ON
Related To: 9555
Action:
$TPROG L%1.dir U1 Restore audio program
$CANM L%1.dir NG%1.exp Cancel all requests from this station
LOG "St %1.phy, %1.dir %1.nam: Guard reset" Send information to System log
$DSPL L%1.dir U2 6000 '' Cmd 60 00: Clear Alarm preparation mode
WUDD %1.phy,%op(%udd(%1.phy),&,65023) Reset Guard Present (bit 9)
WUDD %1.phy,%op(%udd(%1.phy),&,64511) Reset Call Request mode / tamper call (bit 10)
$ST L%1.dir W0 L9554 Stop the alarm-timer
IF %op(%op(%udd(%1.phy),&,256),!=,256) If the cell light was off before "Guard Present"...
IND %1.phy 7 1 1 OFF ...turn light off
@01FF M7C01 U01 W%1.phy U0 ...Send message to AlphaVision
ENDIF
IND %1.phy 0 0 0 OFF Switch off all lamps
@01FF M7C01 U01 W%1.phy U0 Send status message to AlphaVision
If pulse relay is used, the state of the light (on or off) is unknown and the lines in green should be removed.
Power Fail ON - Event Trigger 9556
This event is triggered when the local 24VDC power to the station drops out.
Event Owner: UDP 2 (Prison stations) Event Type: 15 - Event Trigger Feature Sub Event: 0 When Change To: ON Related To: 9556 Action: $STM L%1.dir NG%1.exp U30 '%1.dir Power failure!' U0 Send "Power failure" message to guard group, priority 30 LOG "St %1.phy, %1.dir %1.nam: Power failure" Send information to System log
Power Fail OFF - Event Trigger 9557
This event is triggered when the station is connected to the local 24VDC power.
Event Owner: UDP 2 (Prison stations) Event Type: 15 - Event Trigger Feature Sub Event: 0 When Change To: ON Related To: 9557 Action: $CANM L%1.dir NG%1.exp NM255 U30 Remove "Power failure" message (i.e. all mails with priority 30) LOG "St %1.phy, %1.dir %1.nam: Power failure reset" Send information to System log
Light switch - Event Trigger 9558
This event is triggered when the light button is pressed on the 1007063000 station. It is used to control the lighting in the cell.
Event Owner: UDP 2 (Prison stations)
Event Type: 15 - Event Trigger Feature
Sub Event: 0
When Change To: ON
Related To: 9558
Action:
IF %op(%op(%udd(%1.phy),&,256),==,256) If cell light is currently on...
WUDD %1.phy,%op(%udd(%1.phy),&,65279) ..reset the light status (bit 8)
IND %1.phy 7 1 1 OFF ..switch light off
STOP
ENDIF
WUDD %1.phy,%op(%udd(%1.phy),|,256) If cell light is currently off, set the light status (bit 8)...
IND %1.phy 7 1 1 ON ..and switch the light on. (If pulserelay, light will toggle on both ON and OFF message)
If pulse relay is used, the state of the light (on or off) is unknown and the lines in green should be removed.
Scream Alarm (VOX) - Event Trigger 9561
This event is triggered when the keyswitch is in position 1 or 2, and audio above the specified level is detected.
Event Owner: UDP 2 (Prison stations) Event Type: 15 - Event Trigger Feature Sub Event: 0 When Change To: ON Related To: 9561 Action: IF %op(%op(%udd(%1.phy),&,512),==,512) If "Guard Present" status (bit 9) $STM L%1.dir NG%1.exp U143 '%1.dir Scrm alarm!' U1 Send "Scream alarm" message LOG "St %1.phy, %1.dir %1.nam: Scream alarm!" Send information to System log IND %1.phy 1 1 3 ON Turn call-lamp on, flashing IND %1.phy 4 1 3 ON Turn group-lamp on, flashing IND %1.phy 2 1 1 ON Turn guard present-lamp on @01FF M7C01 U01 W%1.phy U%3.CHG(4,0) Send message to AlphaVision STOP ENDIF
Silent call
The simplex conference feature can be used to silently monitor the prison station. When the prison station is included in a simplex conference this event is triggered, and a command is sent to the station not to switch on the "microphone alive" LED.
Event Owner: UDP 2 (Prison stations) Event Type: 17 - Simplex Conference Member When Change To: ON or OFF Related To: All Action: $DSPL L%1.dir U1 %chg(45,46) '' Disable call LED while in Simplex Conference (monitoring mode).
LOG Conversation start
All conversations will be logged in the System log.
Event Owner: UDP 8 (all stations) Event Type: 7 - Conversation Incoming When Change To: ON Related To: All Action: LOG "Conversation established: %2.dir -> %1.dir" Send information to System log
LOG Conversation end
All conversations will be logged in the System log.
Event Owner: UDP 8 (all stations) Event Type: 7 - Conversation Incoming When Change To: OFF Related To: All Action: LOG "Conversation reset : %2.dir -> %1.dir" Send information to System log
LOG Private Ringing start
Calls in Private Ringing mode will be logged in the System log.
Event Owner: UDP 8 (all stations) Event Type: 9 - Private Ringing mode When Change To: ON Related To: All Action: LOG "Call in private : %2.dir -> %1.dir" Send information to System log
Report faulty stations to AlphaVision
Station errors are reported to AlphaVision via this event. In AlphaVision the station error is displayed by a dedicated icon.
Event Owner: UDP 8 (all stations) Event Type: 13 - Faulty Station line When Change To: ON or OFF Related To: All Action: @01FF M7C06 %1.REF U%3.CHG(1,0) Send status message to AlphaVision
Adding Guard Station in different node
It is possible to add one or more guard stations , analog or IP, in different nodes, but some changes must be done in the Priscom node and the other nodes.
Changes in the other nodes:
- Add guard station as member in group 10, if this is the group used in Priscom node.
- Set flag for "Show Mail in idle" in Users & Statons and Station Type tap.
- Add events for answering call request with M-key or off-hook if wanted.
- Change "Delete Mail Filter" in Exchange & System and Calls & Options from 0 to 3.
Changes in PrisCom node:
- Change event 15 related to 9550. Add @FF in front of command $SM, and change parameter U3 to U11. Command should look like this: @FF $SM L%1.dir NG%1.exp U103 NM18 GV U11 'Call'
- Change command $SM and $STM to @FF $SM and @FF $STM in all events with UDP 2 as owner. This is 10 events in addition to the one in previous point:
- Event 21 related to 9554
- Event 15 related to 9554
- Event 15 related to 9555
- Event 15 related to 9556
- Event 15 related to 9557
- Event 15 related to 9561
- Event 15 related to 9562
- Event 15 related to 9551
- Event 15 related to 9552
- Event 15 related to 9553
Offline mode
When the station is set to offline mode, the inputs an outputs can be used even if the PrisCom station lose communication with the AlphaCom server for any reason. The input and output behavior described in the table below, is the same as the default online behavior. While in offline mode:
Activated Input | Action | Comment |
Call key | Output 1 (L1) = ON Output 4 (L4) = ON LED driver flashing = ON |
Red lamp (Call) Red lamp (Group) External LED |
IN Key1* | Call/Alarm/Tamper OFF Output 2 (L2) = ON Relay = ON |
If activated Green lamp (Present) Cell light |
IN Key2* | Call/Alarm/Tamper OFF Output 2 (L2) = ON Relay = ON |
If activated Green lamp (Present) Cell light |
Input 1 (Pulse) | Output 1 (L1) = ON Output 4 (L4) = ON LED driver flashing = ON |
Red lamp (Call) Red lamp (Group) External LED |
Tamper Switch | Output 3 (L3) = ON | Blue lamp (Tamper) |
* All buttons works as alarm buttons. When IN Key 1 or 2 is deactivated, Output 2 (L2) and the relay is deactivated.