Difference between revisions of "1-4j. RCO, Call indication (solution)"
From Zenitel Wiki
(→Solution) |
(→Solution) |
||
Line 11: | Line 11: | ||
<br style="clear:both;" /> | <br style="clear:both;" /> | ||
− | The | + | For these setting to take effect, the AlphaCom must be restarted. In AlphaPro, press the '''Reset''' button. |
+ | |||
+ | The next step is to create an event that operates the RCO 10 when the right conditions are met. | ||
In '''Users & Stations''', select the station "Main Guard" from the list box, and press the button '''Events'''. '''Insert''' a new event with the following properties: | In '''Users & Stations''', select the station "Main Guard" from the list box, and press the button '''Events'''. '''Insert''' a new event with the following properties: | ||
Revision as of 16:13, 29 June 2016
Solution
Private Ringing indication
- When calling the Main Guard in private ringing mode, a lamp controlled by the relay in the station should be activated when the private ringing starts. (The Main Guard must be set in “Private” mode by pressing the C-key for more than 2 sec.).
- The lamp should be turned off when the private ringing stops.
- Use logical RCO 10 to operate the relay
The first step is to map the logical RCO 10 to the relay of station 400:
For these setting to take effect, the AlphaCom must be restarted. In AlphaPro, press the Reset button.
The next step is to create an event that operates the RCO 10 when the right conditions are met. In Users & Stations, select the station "Main Guard" from the list box, and press the button Events. Insert a new event with the following properties:
Call Queue indication
*When the Main Guard receives a Call Request, the same lamp should be activated to indicate that there is one or more calls in the call queue (Tip: Use event "Priority Mail Present").
- The lamp should be turned off when there are no more calls in the queue.