This is an article explaining in detail how to configure Door Opening.
+
This article explains how to configure the Door Opening feature.
  
 
[[Door opening]] is a standard feature in the AlphaCom. The way it works is that when an operator is in a conversation with a door station, the operator kan press digit 6 to activate a relay.  
 
[[Door opening]] is a standard feature in the AlphaCom. The way it works is that when an operator is in a conversation with a door station, the operator kan press digit 6 to activate a relay.  

Revision as of 13:42, 1 February 2017

AlphaCom icon 300px.png

This article explains how to configure the Door Opening feature.

Door opening is a standard feature in the AlphaCom. The way it works is that when an operator is in a conversation with a door station, the operator kan press digit 6 to activate a relay.

Event Handler

We need to define who this event is for, and which output to activate. This is done using the Event Handler. Go to Exchange & System menu from the top menu in AlphaPro:

AlphaPro Exchange and System icon.png


From the Exchange&System window choose the Events button:

Exchange System Events.png


In the Event Actions window click the Insert button and create an event like this:

EventHandler Event2.PNG


This event is triggered when the operator dials digit 6 while in covnersation with the door. Physical number 6 (the door station) is the owner of the event. When Related To can be set to "All", meaning whoever in conversation with the door is allowed to dial digit 6 to open the door. In this example we have chosen to limit this access by selecting a single station; Directory number 120.

In the example above RCO 6 will be triggered when the Door Opening feature (digit 6) is pressed.

Mapping of RCO

The actual physical output that is activated is dependent on the station type.

IP Stations

All IP Substations have an inbuilt relay which can be controlled by the RCO command. In the RCO table the RCO can be mapped to relay of the station. From Exchange & System menu choose the RCO button:

Exchange System RCO.png


Select the RCO from the list on the left and click the Change button:

RCO Change.png


Choose RCO Type = Station, and enter the physical number of the door station (where the relay is physically located) in the Station field:

RCO Change2.PNG


Which Pin Number to use depends on the station type:


Analogue stations

If the door station is analogue the RCO comes from the server its self. On an [XE7]] there are two connectors for RCO1-6 and 7-12 located on the back:

XE7 RCO Connectors.png


On XE20/XE26 there is an RCO output per ASLT connection. These can be fetched either from

Subscriber Connection Board RCO.png


RJ45 Connection RCO.png


The RCO, which is a logical signal must be connected to a relay. Use the Multi Relay Board for this. See MRBD article for further details.

Finalization

Close all windows in AlphaPro and upload the database using the Send All or Send Change button. Apply changes by restarting the server.