Actions

Difference between revisions of "Dynamic group call"

From Zenitel Wiki

(Event Handler configuration)
(Event Handler configuration)
Line 46: Line 46:
 
Event 2: Include members
 
Event 2: Include members
 
*When DAK keys are pressed, turn on the green LED, and include the station or local group to the dynamic group
 
*When DAK keys are pressed, turn on the green LED, and include the station or local group to the dynamic group
*If the DAK key pressed is the "Group Configuration" button (9535), disconnect the station from configuration mode, and dispatch the dynamic group call
+
*If the DAK key pressed is the "Group Configuration" button (9535), disconnect the station from configuration mode, turn off the red LED, and dispatch the dynamic group call
 
 
 
 
  
 
[[File:DynGrp Event2.PNG|thumb|left|500px|"Group Configuration" button]]
 
[[File:DynGrp Event2.PNG|thumb|left|500px|"Group Configuration" button]]

Revision as of 12:28, 27 May 2021

AlphaCom icon 300px.png

Operation

  • Press a dedicated "Group Configursation" DAK key. The red led in key starts flashing, and the Dynamic Group is emptied.
  • Select stations or local groups to be included by pressing the associated DAK keys. A steady green led in the keys indicates that the stations/groups are included
  • Press the "Group Configuration" button again, and the group call is activated (the ding-dong chime is played). Pressing the `M`-key opens the microphone.
  • The green leds continue to be lit during the group call
  • Cancel the group call by pressing the `C`-key. The green LEDs are turned off.

For best performance it is recommended to use CRM V station or ECPIR-3P panel, as these devices have buttons with LEDs showing status.

Software requirements

  • ICX: Any version
  • AlphaCom: 13.0.3.0 or later

Configuration

  • Assign directory number 9535 to DAK 1 of the operator station. This is the Group Configuration button. Directory number 9535 is included in a default database.
"Group Configuration" button


  • Each operator station is assigned its own Dynamic Group Call by entering the Dynamic Group Call number in the User Defined Parameter (%1.EXP) field of the operator.
  • Include operator stations in UDP group 1. Name the UDP group e.g. "Operators".
Include the operator station in UDP Group 1, and enter the directory number of the Dynamic Group used by this operator (Here: 899)



Event Handler configuration

In AlphaPro, go to Exchange and System -> Events, press Insert and create the following events (Simply copy/paste the action strings below into AlphaPro):

Event 1: Start/stop Group Configuration

  • When the "Group Configuration" button is pressed, empty the Dynamic Group and turn on red LED in button.
  • When leaving the Group Configuration mode, start a 1 sec timer. If the Dynamic Group is not activated within this time, the LEDs will be cleared.
"Group Configuration" button


IF %chg(1,0)
$GRM LV L%1.exp U3
IND %1.phy %1.dak(I%2.dir) 1 3 ON
stop
ENDIF
$ST L%1.dir W10 L%1.exp


Event 2: Include members

  • When DAK keys are pressed, turn on the green LED, and include the station or local group to the dynamic group
  • If the DAK key pressed is the "Group Configuration" button (9535), disconnect the station from configuration mode, turn off the red LED, and dispatch the dynamic group call
"Group Configuration" button


IND %1.phy %1.dak(I%2.dir) 2 1 ON 
$GRM L%2.dir L%1.exp U1
IF %op(%2.dir,=,9535)
$DISCON_ST L%1.dir 0
IND %1.phy %1.dak(I%2.dir) 1 3 OFF
PAUSE
PAUSE
PAUSE
$DD L%1.dir L%1.exp


"Group Configuration" button


IF %op(%2.dir,=,%1.exp)
IF %chg(1,0)
$ST L%1.dir W0 L%1.exp
stop
ENDIF
IND %1.phy 0 0 0 OFF
ENDIF


"Group Configuration" button


IF %op(%2.dir,=,%1.exp)
IND %1.phy 0 0 0 OFF
ENDIF