A master station should be able to disable calls from substations for a periode of time.
In the programming example below the master station dials 9535 + substation number to disable calls from that substation for 15 minutes.
Directory number 9535 is a two-step event trigger, feature 95/0. When dialled, an event type 25 is triggered and the action string $SSC L%2.dir U2 moves the station to COS 2. COS 2 is by default empty, which will prevent calls to be initiated. Also a 15 minute timer is started, $ST L%2.dir W9000 L9999. The timer will trigger event type 21 when timing out. Command $SSC L%2.dir U1 will then move the station back to COS 1.
Event 1 - Move the substation to COS 2:
| Event Owner: | The Master Station |
| Event type: | 25 – Event trigger with parameter |
| Subevent: | 0 |
| When change to: | ON |
| When related to: | All |
| Action: | $SSC L%2.dir U2 |
| $ST L%2.dir W9000 L9999 |
Event 2 - Move the substation back to COS 1:
| Event Owner: | Stations w/UDP Id: 8 (All stations) |
| Event type: | 21 – Event timer |
| When change to: | ON |
| When related to: | Directory number: 9999 |
| Action: | $SSC L%2.dir U1 |