In the programming example below the master station dials 9535 + substation directory number to disable calls from that substation for 15 minutes.  
 
In the programming example below the master station dials 9535 + substation directory number to disable calls from that substation for 15 minutes.  
  
Directory number 9535 is by default a two-step event trigger, [[Event_Trigger_w/User_Parameter|feature 95/0]]. When 9535 + Substation is dialled, an [[Event_Trigger_with_parameter_%28Event_Type%29|event type 25]] is triggered and the action string '''[[SET_STATION_COS|$SSC L%2.dir U2]]''' moves the substation to [[COS]] 2. COS 2 is by default empty, which will prevent calls to be initiated. The command '''[[DISCON_ST|$DISCON_ST L%1.dir U2]]''' will disconnect the master station with a success tone after having entered the substation number. Also a 15 minute timer is started by the command '''[[SET_TIMER|$ST L%2.dir W9000 L9999]]'''. The timer will trigger [[Event_Timeout_%28Event_Type%29|event type 21]] when it times out, and the command '''$SSC L%1.dir U1''' will move the station back to COS 1, and calls can again be made.
+
Directory number 9535 is by default a two-step event trigger, [[Event_Trigger_w/User_Parameter|feature 95/0]]. When 9535 + Substation is dialled, an [[Event_Trigger_with_parameter_%28Event_Type%29|event type 25]] is triggered and the action string '''[[SET_STATION_COS|$SSC L%2.dir U2]]''' moves the substation to [[COS]] 2. COS 2 is by default empty, which will prevent calls to be initiated. The command '''[[DISCON_ST|$DISCON_ST L%1.dir U2]]''' will disconnect the master station with a success tone after having entered the substation number. A 15 minute timer is started by the command '''[[SET_TIMER|$ST L%2.dir W9000 L9999]]'''. When the timer expires it will trigger [[Event_Timeout_%28Event_Type%29|event type 21]], and the command '''$SSC L%1.dir U1''' will move the station back to COS 1, and calls can again be made.
  
 
------------
 
------------

Revision as of 14:58, 21 August 2008

Situation

A master station should be able to disable calls from substations for a periode of time.

Solution

In the programming example below the master station dials 9535 + substation directory number to disable calls from that substation for 15 minutes.

Directory number 9535 is by default a two-step event trigger, feature 95/0. When 9535 + Substation is dialled, an event type 25 is triggered and the action string $SSC L%2.dir U2 moves the substation to COS 2. COS 2 is by default empty, which will prevent calls to be initiated. The command $DISCON_ST L%1.dir U2 will disconnect the master station with a success tone after having entered the substation number. A 15 minute timer is started by the command $ST L%2.dir W9000 L9999. When the timer expires it will trigger event type 21, and the command $SSC L%1.dir U1 will move the station back to COS 1, and calls can again be made.


Event 1 - Move the substation to COS 2, start a timer, and disconnect the master station:

Event Owner: The Master Station
Event type: 25 – Event trigger with parameter
Subevent: 0
When change to: ON
When related to: All
Action: $SSC L%2.dir U2
  $ST L%2.dir W9000 L9999
  $DISCON_ST L%1.dir U2



Event 2 - Move the substation back to COS 1:

Event Owner: Stations w/UDP Id: 8 (All stations)
Event type: 21 – Event timer
When change to: ON
When related to: Directory number: 9999
Action: $SSC L%1.dir U1