This article describes how a master station can disable substations from making calls for a periode of time. | This article describes how a master station can disable substations from making calls for a periode of time. | ||
Revision as of 15:00, 21 August 2008
This article describes how a master station can disable substations from making calls for a periode of time.
Solution
In the programming example below the master station dials 9535 + substation directory number to disable calls from that substation for 15 minutes.
Directory number 9535 is by default a two-step event trigger, feature 95/0. When 9535 + Substation is dialled, an event type 25 is triggered and the action string $SSC L%2.dir U2 moves the substation to COS 2. COS 2 is by default empty, which will prevent calls to be initiated. The command $DISCON_ST L%1.dir U2 will disconnect the master station with a success tone after having entered the substation number. A 15 minute timer is started by the command $ST L%2.dir W9000 L9999. When the timer expires it will trigger event type 21, and the command $SSC L%1.dir U1 will move the station back to COS 1, and calls can again be made.
Event 1 - Move the substation to COS 2, start a timer, and disconnect the master station:
Event Owner: | The Master Station |
Event type: | 25 – Event trigger with parameter |
Subevent: | 0 |
When change to: | ON |
When related to: | All |
Action: | $SSC L%2.dir U2 |
$ST L%2.dir W9000 L9999 | |
$DISCON_ST L%1.dir U2 |
Event 2 - Move the substation back to COS 1:
Event Owner: | Stations w/UDP Id: 8 (All stations) |
Event type: | 21 – Event timer |
When change to: | ON |
When related to: | Directory number: 9999 |
Action: | $SSC L%1.dir U1 |