Actions

Difference between revisions of "Adding additional relay(s) to a Zenitel IP Device"

From Zenitel Wiki

(Connection)
 
(41 intermediate revisions by 2 users not shown)
Line 1: Line 1:
[[File:1009970200.PNG|thumb|300px|MRBD]]
+
[[File:1009970200.PNG|thumb|300px|MRBD - Multi Relay Board (1009970200)]]
The [[:Category:Stations#Turbine_stations|Turbine Compact series]] intercom stations and the [[TKIS-2|TKIS-2 VoIP module]] have 6 I/O's which when set as outputs can be used together with the conventional Multi Relay Board ([[MRBD]]) to give up to 6 additional relay contacts.
 
  
All 6 relays on the MRBD are double pole, double throw (DPDT) contacts.
+
Most  [[:Category:Stations#Turbine_stations|Zenitel IP Stations and Devices]] are equipped with 6 I/O's which, when set as outputs, can be used together with the conventional [[MRBD|Multi Relay Board (MRBD)]] to give up to 6 additional relay contacts.
 +
 
 +
The relays on the MRBD are double pole, double throw (DPDT) contacts.
  
 
==Requirements==
 
==Requirements==
Line 8: Line 9:
 
*'''Software''': The Turbine Station must have sw version TCIS-3.0.3.3 or newer.
 
*'''Software''': The Turbine Station must have sw version TCIS-3.0.3.3 or newer.
  
==MRBD Configuration==
+
==MRBD Jumper Settings==
The MRBD has 6 jumpers (S1-S6) which allows to set the relays individually to be used with AlphaCom system (active "high" signal) or the older TouchLine system (active "low" signal). Default the MRBD comes with the jumpers set for AlphaCom mode.
+
The MRBD has 6 jumpers (S1-S6) which determines if the relay should be triggered on active "high" signal or active "low" signal. When used with a Zenitel IP Device, the associated jumper must be set to "TouchLine" as indicated in the drawing below.
 +
[[File:MRBD-4.PNG|left|thumb|600px|MRBD Jumper Settings: Set to "TouchLine" when used with Zenitel Devices]]
 +
<br style="clear:both;" />
  
When a relay is used with Turbine, the associated jumper must be set to "TouchLine"
+
==Connection==
[[File:MRBD-4.PNG|left|thumb|500px|MRBD Jumper Settings: Set to "TouchLine" when used with Turbine stations]]
+
The MRBD must be powered by an external 24VDC power supply.  
<br style="clear:both;" />
 
  
See [[MRBD - Relay Board]] for more details on the Multi Relay Board.
+
The same power supply must be connected also to the Zenitel IP device, regardless if it is powered by PoE or not.
<br style="clear:both;" />
 
  
==Connection==
+
Connect the power and I/Os according to the below drawing:
The MRBD is powered by 24VDC. This power can be retrieved from AlphaCom Audio Servers XE7, XE20 and XE26 (the latter with additional [[PDB|PDB Board]]).
 
  
*Connect the 0V from the Turbine Compact to the GND on the MRBD
+
[[File:MRBD Turbine.png|left|thumb|700px|Connection diagram]]
*Connect the I/O('s) from the Turbine Compact to the Input(s) on the MRBD
 
[[File:TCIS_MRBD.png|left|thumb|500px| Turbine - MRBD connection diagram]]
 
 
<br style="clear:both;" />
 
<br style="clear:both;" />
  
See [[TCIS Connections]] for more details on Turbine Compact connections.
+
See [[Turbine Compact series board connectors]] for more details on Turbine Compact connections.
 
<br style="clear:both;" />
 
<br style="clear:both;" />
  
 
{{Warn|
 
{{Warn|
* ''It is recommended to power the TKIS from the same 24VDC power supply as used for the MRBD board.''
+
* ''The MRBD board and the Zenitel IP Device must be powered from the same 24VDC power supply, regardless if the Device is powered by PoE or not.''
* ''The reason is that if the TKIS is powered by PoE, all relays will be activated if the PoE power disappears while the MRBD is still powered from the 24VDC power supply'' }}
+
* ''The reason is that if the Device is powered by PoE only, all relays will be activated if the PoE power disappears while the MRBD is still powered from the 24VDC power supply'' }}
  
==Turbine Web configuration==
+
==Device Web configuration==
The Turbine station must be configured to register to the AlphaCom in the standard way. In addition the I/O's used with the MRBD must be set to '''Outputs'''.
+
The Zenitel Device must be configured to register to the ICX-AlphaCom in the standard way. In addition the I/O's used with the MRBD must be set to '''Outputs'''.
  
[[Turbine_Configuration#Logging_into_the_Station|Log on]] to the Turbine station and navigate to '''Advanced AlphaCom -> I/O Settings.
+
[[Logging into an Zenitel IP Device|Log on]] to the Device and navigate to '''Advanced AlphaCom -> I/O Settings.
  
 
Set the I/O('s) that are connected to the MRBD as '''Output'''.
 
Set the I/O('s) that are connected to the MRBD as '''Output'''.
[[File:TKIS-MRBD-1.png|left|thumb|500px|In the Turbine web interface, set the required I/O's as outputs]]
+
[[File:Output Web.png|left|thumb|700px|In the Device web interface, set the required I/O's as outputs]]
<br style="clear:both;" />
 
 
 
See [[Turbine Configuration]] for more details on configuring the Turbine Compact.
 
 
<br style="clear:both;" />
 
<br style="clear:both;" />
  
 
==AlphaPro configuration==
 
==AlphaPro configuration==
The Turbine Compact station (or [[TKIS-2|TKIS-2 Kit]]) must be defined in AlphaPro as a CCoIP station.
+
The outputs of the Zenitel Device must be mapped to logical RCO's (Remote Control Output).  
[[File:TKIS-MRBD-2.png|left|thumb|500px]]
+
This is done from [[AlphaPro]]. In '''Exchange & System''' -> '''RCO''' select a free RCO.
<br style="clear:both;" />
 
 
 
===RCO mapping ===
 
The outputs of the Turbine station must be mapped to logical RCO's in the AlphaCom.  
 
In '''Exchange & System''' -> '''RCO''' select a free RCO and press change.
 
 
* ''RCO Type'': Change to '''Station'''.  
 
* ''RCO Type'': Change to '''Station'''.  
* ''Station'': Enter the physical number of the Turbine Compact
+
* ''Station'': Enter the ''physical'' number of the Zenitel Device
* ''Pin Number'': Enter the output (1-6) to be controlled by that logical RCO
+
* ''Pin Number'': Enter the output (1-6) to be related to that logical RCO
 
[[File:TKIS-MRBD-3.png|left|thumb|500px|Output 1 of station 33 (Directory number 133) is mapped to logical RCO 34]]
 
[[File:TKIS-MRBD-3.png|left|thumb|500px|Output 1 of station 33 (Directory number 133) is mapped to logical RCO 34]]
[[File:TKIS-MRBD-4.png|left|thumb|500px|Output 6 of station 33 (Directory number 133) is mapped to logical RCO 39]]
 
 
<br style="clear:both;" />
 
<br style="clear:both;" />
  
===Events===
 
The RCO's are controlled from the [[Event Handler]].
 
Here are three practical examples:
 
-----
 
====Controlling the door lock ====
 
RCO 34 controls output 1 on the Turbine Compact. When this event is triggered relay 1 on the MRBD is activated for 3.5 seconds.
 
[[File:TKIS-MRBD-5.png|left|thumb|500px]]
 
<br style="clear:both;" />
 
-----
 
====Activating a rotating lamp on incoming call ====
 
This event triggers when someone is calling the Main Guard which is in Private Mode. It will activate RCO 35, which is physically output 2 on the TKIS-2 with physical number 33. This output controls relay 2 on the MRBD which when activated turns on a rotating lamp to alert the Main Guard that there is an incoming call.
 
[[File:TKIS-MRBD-6.png|left|thumb|500px]]
 
<br style="clear:both;" />
 
-----
 
====Opening a barrier at a predefined time====
 
This event will trigger at 7am from Monday to Friday. It will activate RCO 36 which is output number 3 on the TKIS. This in turn operates relay 3 on the MRBD, and the barrier is raised.
 
[[File:TKIS-MRBD-7.png|left|thumb|500px]]
 
<br style="clear:both;" />
 
  
===Upload Data===
+
The logical RCO's are controlled from the [[Event Handler]]. Configuration examples:
When AlphaPro configuration is finished, upload the data by pressing ''Send All'' or ''Send Change'' from the top menu. After the upload is complete reset the exchange to make the changes take effect.
+
* [[Door Opening - Configuration example]]
<br style="clear:both;" />
 
  
 
=Related Articles=
 
=Related Articles=

Latest revision as of 16:23, 23 June 2023

MRBD - Multi Relay Board (1009970200)

Most Zenitel IP Stations and Devices are equipped with 6 I/O's which, when set as outputs, can be used together with the conventional Multi Relay Board (MRBD) to give up to 6 additional relay contacts.

The relays on the MRBD are double pole, double throw (DPDT) contacts.

Requirements

  • Hardware: The Turbine station must be produced week 37 of 2012 or later.
  • Software: The Turbine Station must have sw version TCIS-3.0.3.3 or newer.

MRBD Jumper Settings

The MRBD has 6 jumpers (S1-S6) which determines if the relay should be triggered on active "high" signal or active "low" signal. When used with a Zenitel IP Device, the associated jumper must be set to "TouchLine" as indicated in the drawing below.

MRBD Jumper Settings: Set to "TouchLine" when used with Zenitel Devices


Connection

The MRBD must be powered by an external 24VDC power supply.

The same power supply must be connected also to the Zenitel IP device, regardless if it is powered by PoE or not.

Connect the power and I/Os according to the below drawing:

Connection diagram


See Turbine Compact series board connectors for more details on Turbine Compact connections.

Warning icon
  • The MRBD board and the Zenitel IP Device must be powered from the same 24VDC power supply, regardless if the Device is powered by PoE or not.
  • The reason is that if the Device is powered by PoE only, all relays will be activated if the PoE power disappears while the MRBD is still powered from the 24VDC power supply


Device Web configuration

The Zenitel Device must be configured to register to the ICX-AlphaCom in the standard way. In addition the I/O's used with the MRBD must be set to Outputs.

Log on to the Device and navigate to Advanced AlphaCom -> I/O Settings.

Set the I/O('s) that are connected to the MRBD as Output.

In the Device web interface, set the required I/O's as outputs


AlphaPro configuration

The outputs of the Zenitel Device must be mapped to logical RCO's (Remote Control Output). This is done from AlphaPro. In Exchange & System -> RCO select a free RCO.

  • RCO Type: Change to Station.
  • Station: Enter the physical number of the Zenitel Device
  • Pin Number: Enter the output (1-6) to be related to that logical RCO
Output 1 of station 33 (Directory number 133) is mapped to logical RCO 34



The logical RCO's are controlled from the Event Handler. Configuration examples: